目录一、XX大学课程设计(论文)任务书.............................................1二、原始条件:上海某商场地下停车场通风及排烟设计................2三、方案设计........................................................................................2四、排风、排烟量的计算....................................................................2五、水利计算........................................................................................3六、阻力计算........................................................................................4七、设备的选择....................................................................................5八、设计总结........................................................................................6九、设计参考资料................................................................................7十、附表................................................................................................8一、XX大学课程设计(论文)任务书院(系):基层教学单位:学号070107030031学生姓名XX专业(班级)建环07-2班设计题目上海某商场地下停车场通风及排烟设计设计技术参数1、地点:上海2、建筑形式:地下室3、层高:4.5m4、层数:1设计要求1、说明书应按工业通风课程设计大纲和指导书要求撰写;2、说明书用B5纸打印,正文用5号宋体,文中数据表格用小5号字体,标题用4号黑体,行距为1.25倍,页数不少于10页。工作量1、拟定方案2、计算:送、排风(或排烟)风量计算、水力计算、压力不平衡计算等;3、设备选择:查找手册或样本资料,选择风管、风机、防火阀、送(排)风口形式等;4、绘图:绘图工具为电脑CAD,图纸共计2-3张,即平面图、系统图,同时及必要位置大样图、剖视图及设计施工说明,图纸用A3纸打印;工作计划1、熟悉工程概况,查找、阅读相关资料1天2、构想方案,系统分区,送、排风风量及排烟、补风量计算1天3、风口及风管布置,水力计算及不平衡调整2天5、风口、阀门、风机等设备选型1天6、图纸综合绘制、修改及编制设计说明书3天7、打印图纸、说明书,准备答辩2天参考资料1)《工业通风》(第三版)孙一坚主编,中国建筑工业出版社2)《简明通风设计手册》孙一坚主编,中国建筑工业出版社3)《实用供热空调设计手册》(第二版)陆耀庆主编中国建筑工业出版社4)《汽车库、修车库、停车场设计防火规范》(GB50067-97)5)《全国民用建筑工程设计技术措施-暖通空调·动力》(2009)6)《建筑防火设计规范》(GB50016-2006)其它参考资料见《工业通风课程设计》大纲指导教师签字基层教学单位主任签字说明:此表一式四份,学生、指导教师、基层教学单位、系部各一份。年月日燕山大学课程设计说明书2二、原始条件:上海某商场地下停车场通风及排烟设计1、地点:上海2、建筑形式:地下车库3、层高:4.5m4、层数:-1三、方案设计1、全面通风,采用机械排风、排烟合用系统,车道自然进风,火灾时机械补风的通风方式。排风口和排烟口分设,采用相应阀门控制。2、整个车库按一个防火分区两个防烟分区计算。3、本设计中排风量按车库换气次数6次/h计算,排烟量按6次/h计算。补风量按排烟量的60%计算。4、每个排风支管均配套安装70℃防烟防火调节阀。4、平时通风时,防火排烟阀打开,风机处于通风工况;发生火灾时,防灾中心输出信号;使排烟口打开,并联动风机转为排烟工况;当烟气温度达到70℃时防火阀关闭;当烟气温度达到280℃时,所有防火排烟阀关闭,并联动风机关闭。5、风管采用镀锌钢板咬口制作,法兰连接6、水平风管支吊架间距均为3m,垂直风管支吊架间距不大于4m;防火排烟阀单独设置支吊架,气流方向与阀体所示方向应一致。7、每个直角弯头均应装设导流叶片,柔性短管不能作异径接管使用;每个水平支管均应设风量测定孔,应设于风管中心线上。四、排风、排烟量的计算设有机械排烟系统的汽车库,其每个防烟分区的建筑面积不宜超过2000m2,防烟分区不应跨越防火分区。防烟分区可采用挡烟垂壁、隔墙或从顶棚下突出不小于0.5m的梁划分。[5]p12根据对车库的具体分析,决定设两个防烟分区进行系统设计,为A区和B区,具体分区见图纸。各区风量计算见下:A区:面积S=1527㎡排风量:层高>3m按3m计算,按6次/h换气量计算故Q=1527×3×6=27486m³/h排烟量:按实际层高h=4.5m计算,按6次/h换气量计算故Q=1527×4.5×6=41229m³/h补风量:按排烟量的60%计算故Q=41229×60%=24737m³/hB区:面积S=1192㎡排风量:层高按h=3m,换气次数按6次/h换气量故Q=1192×2×6=21456m³/h排烟量:Q=1192×4.5×6=32184m³/h燕山大学课程设计说明书3补风量:按排烟量的60%计算故Q=32184×60%=19310m³/h五、水利计算A区:设计系统有5个排烟口,18个排风口。每个排烟风口承担8246m³/h的排烟量,每个排风口承担1527的排风口,排烟口安装在风管干管上,排风口安装在支管上。其位置见图纸。机械排烟管道风速,采用金属管道时不应大于20m/s;采用内表面光滑的非金属材料风道时,不应大于15m/s,排烟口的风速不宜超过10m/s。机械通风干管流速为5m/s到8m/s,支管流速为2m/s到5m/s,排风口流速为4m/s到5m/s。[2]p254各管段管径及流速见下表:序号风量(m^3/h)管宽(mm)管高(mm)流速(m/s)序号风量(m^3/h)管宽(mm)管高(mm)流速(m/s)115275003202.6511415275003202.651230545003205.3021530545003205.302361086304006.7331615275003202.651491628005006.3621730545003205.30251221610005006.7871815275003202.65161527010006306.7331930545003205.30271832412506306.4632015275003202.65182137812506307.5412130545003205.30292443212508006.7872215275003202.651102748612508007.6352330545003205.3021130545003205.3022415275003202.6511215275003202.6512530545003205.3021330545003205.3022615275003202.651注:管段序号与轴测图相对应。排风口用单层顶装百叶,尺寸都相同,为500×200mm,流速为3.44m/s。排烟风口为侧装与排风干管上的多页排烟口,各排烟风口尺寸及风速见下表序号123456所在管段号2246810尺寸(mm×mm)600×300600×300750×450750×450750×450750×450流速(m/s)9.099.099.709.709.709.70B区:各管段管径及流速见下表:序号风量(m^3/h)管宽(mm)管高(mm)流速(m/s)序号风量(m^3/h)管宽(mm)管高(mm)流速(m/s)110735002502.3841621465002504.769221465002504.7691710735002502.384燕山大学课程设计说明书4342926303205.9141821465002504.769464386305005.6771910735002502.384585848005005.9612021465002504.7696107308006305.9142110735002502.38471287610006305.6772221465002504.76981502212506305.2992310735002502.38491716812506306.0562421465002504.769101931412506306.8132510735002502.384112146012506307.572621465002504.7691221465002504.7692710735002502.3841310735002502.3842821465002504.7691421465002504.7692910735002502.3841510735002502.384排风口用单层顶装百叶,尺寸都相同,为400×250mm,流速为4.26m/s。排烟风口为侧装与排风干管上的多页排烟口,各排烟风口尺寸及风速见下表序号123456所在管段号2246810尺寸(mm×mm)700×200700×200700×350600×400600×400600×400流速(m/s)9.129.1210.4310.6410.6410.64补风系统,两区共用一根补风管,补风量区两区补风量最大值。各管段尺寸及流速见下表。序号风量(m^3/h)管宽(mm)管高(mm)流速(m/s)149476304005.453298948005006.87131484110006306.54441978810008006.87152473512508006.871各补风口尺寸均相同,为500×300mm,流速为6.28m/s。六、阻力计算阻力计算见附表阻力平衡计算A区排风管:最不利环路ΔP=ΔP1+……+ΔP10=329.74paA点:ΔP3+……+ΔP12=318.90pa,不平衡率=(329.74-318.90)/329.74=3.2%B点:ΔP4+……ΔP10+ΔP13+ΔP14=304.20pa,不平衡率=(329.74-304.20)/329.74=7.7%燕山大学课程设计说明书5C点:ΔP5+……+ΔP10+ΔP15+ΔP16=300.10pa,不平衡率=(329.74-300.10)/329.7=8.9%D点:ΔP6+……+ΔP10+ΔP17+ΔP18=290.1pa,不平衡率=(329.74-290.10)/329.74=12.0%E点:ΔP7+……+ΔP10+ΔP19+ΔP20=271.32pa,不平衡率=(329.74-271.32)/329.74=17.7%F点:ΔP8+……+ΔP10+ΔP21+ΔP22=259.73pa,不平衡率=(329.74-259.73)/329.74=21.2%G点;ΔP9+ΔP10+ΔP23+ΔP24=244.3pa,不平衡率=(329.7-244.3)/329.7=25.9%H点:ΔP10+ΔP25+ΔP26=232.82pa,不平衡率=(329.74-232.82)/232.82=29.4%B区排风管:最不利环路ΔP=ΔP1+……+ΔP11=196.42paA点:ΔP3+……+ΔP13=193.63pa,不平衡率=(196.42-193.