1气体灭火系统安装工程施工组织设计方案北京科华消防工程有限公司石景山分公司2011年1月04日2目录封面·································································1目录·································································2一、编制依据··································································3二、工程概况··································································3三、项目部组织结构·························································4四、施工配合及保证措施···················································6五、施工方法及质量保证方案·············································6六、重要部位质量通病及防治办法·······································17七、工期及保证措施·························································22八、安全文明环境施工保证措施··········································22九、工程项目竣工验收······················································25十、售后服务及维保制度···················································273一.编制依据甲方提供的设计图纸及招标文件1.《建筑设计防火规范》(GB50016—2006)2.《二氧化碳灭火系统设计规范》(GB50193-93,99年版)3.《气体灭火系统施工及验收规范》(GB50263—2007)4.《建筑电气通用图集》(92DQ9);5.《电气安装施工图册》;6.《建筑设备安装分项施工工艺标准》(建工集团92年);7.《建筑安装工程质量检验评定统一标准》(GBJ300-88);8.《火灾自动报警系统施工与验收规范》(GB50166-92)9.《消防联动控制设备通用技术条件》(GB16806-1997);二、工程概况1.工程名称:交通部档案馆气体灭火系统工程2.建筑面积:约600平方米。3工程内容:消防气体灭火及联动系统。4.工程介绍:交通部档案室分地下一、地下二两层。地下一层共有七个房间,结合防护区的建筑特点采用有管网式高压二氧化碳气体全淹没灭火系统;地下二层共有七个房间,结合防护区的建筑特点,将7个防护区设计为七氟丙烷无管网灭火系统。针对本工程的特点,充分认识到工程对施工质量,施工工艺标准的严格要求,我公司将重点从科学的施工组织;优化的施工程序;先进的施工方法;有效的技术组织措4施;严格的质量保证措施;及时、合理的组织施工进度及管理等方面做出规划,确保实现工程质量达到甲方的要求。为搞好北京交通部档案室工程的施工,全面贯彻落实施工企业ISO9001:2000体系,保证工程的顺利实施,确保质量,保证工期,圆满地完成整个工程。我们根据贵单位提供的设计院的设计方案,特制定以下施工组织设计方案,并严格按此方案执行。三.项目部组织结构1、组织结构图如下:2、施工管理在工程施工阶段,公司组成一个专门的项目组,对工作时间、劳项目经理工程主管材料供应部公司安全员现场安全施工队长技术部资料员质量管理处其它焊工组电工组5动纪律统一管理;工地成员统一着装,佩带工牌,并签定安全责任书。这个项目组的组成及职责范围如下:1)项目经理:职责:负责整个工程的系统管理,人员调度,技术支援,协调与甲方及其他管理部门的关系,签送工程联系单,组织工作人员编制整个工程的进程计划表,指导现场工程人员施工。工程结束后组织有关人员进行最后的验收。2)质量管理处职责:负责工程施工中各个工种、各个工序的工程质量整体工程的质量管理,监督各部门的质量落实情况;并参与甲方、监理的与本工程有关的隐蔽工程验收工作。3)工程主管:职责:负责工程施工中各个工种、各个工序的工程质量整体工程的质量管理。负责施工现场的施工及施工人员的安排,带领施工人员规范施工,作好施工记录,负责工程中的具体技术问题的解决,向项目经理及公司汇报施工完成情况,签字负责。4)材料供应部:根据施工队长工程进度,工程主管提出材料及工具等采购要求、交项目经理批准,填写材料申购单,交公司采购或现场采购。5)技术部:负责施工图纸技术交底,经项目经理、工程主管内部交底,确保工期及施工进度。66)资料员:负责施工过程所有技术资料、图纸、工作联系函、隐蔽工程记录、质量评定表、监理会议纪要、施工记录内容等相关文件汇总分类。7)安全员:负责工程施工现场、生活区等临时用电的保护,急电设备安全规范操作等进行定时检查,发现隐患及时改正,督促施工人员安全施工。负责施工过程的安全生产,制定安全治安条例,加强安全培训,确保纪律严明,安全大计。四、施工配合及保证措施在该项工程的施工过程中,为保证工程的进度和质量,我们积极与甲方施工管理人员配合,以保证甲方的要求自始自终得到贯彻。同时能及时解决施工过程中施工条件不足的问题。1、必备的施工条件:A、甲方指派专人负责与我方协调和配合;B、甲方提供现场施工电源、水源和其他必要的施工条件(三通一平)。C、我方在接到甲方进场施工通知和现场条件具备的情况下,三天内进场施工,施工材料进入施工场地。2、施工期间,由于甲方原因或其他出现设计方案的更改或使用材料方面的更改的,我方现场工程主管会积极与甲方联系,及时把甲方的意见和建议转告项目经理,并及时作出更改方案图和更改说明,待甲方签字认可后,我方进行更改施工。五、施工方法及质量保证方案7针对档案室消防气体灭火系统的具体情况,提出以下的总体施工方案:1.为了保证施工质量,必须严格按规范规程进行施工。2.考虑本次工程的工期,故在其人员的配置上基本保持其固定性。3.必须严格按以下的施工注意事项和要求进行安全施工。(一)消防报警及联动系统工程:1、系统管线的施工要求:A.火灾自动报警系统的传输线路和50下供电的控制线路,应采用电压等级不低于交流250V的铜芯绝缘导线或铜芯电缆。采用交流220/380V的供电和控制线路应采用电压等级不低于交流500V的铜芯绝缘导线或铜芯电缆。B.火灾自动报警系统的传输入线路采用穿金属管、经阻燃处理的硬质塑料管或封闭式线槽保护方式布线。C.消防控制、通信和警报线路采用金属管或金属线槽保护,并应在金属管或金属线槽上采取防火保护措施。D.不同系统、不同电压等级、不同电流类别的线路,不应穿在同一管内或线槽的同一槽孔中。E.火灾自动报警系统导线敷设后,应对每回路的导线用500V的兆欧表测量绝缘电阻,其对地绝缘电阻不应小于20MΩ。2、安装光电感烟探测器时应注意的事项:A.本次工程在梁的顶棚上设置感烟探测器时,应符合下列规定:a.当梁突出顶棚的高度小于200mm时,可不计梁对探测器保护面积的8影响。b.当梁突出顶棚的高度为200-600mm时,应确定梁对探测器保护面积的影响和一只探测器能够保护的梁间区域的个数。c.当梁突出顶棚的高度超过600mm时,被梁隔断的每个梁间区域至少应设置一只探测器。d.当梁间净距小于1m时,可不计梁对探测器保护面积的影响。B.在宽度小于3m的内走道顶棚上设置探测器时,宜居中布置。感温探测器的安装间距不应超过10m;感烟探测器的安装间距不应超过15m;探测器至端墙的距离,不应大于探测器安装间距的一半。这在两超市的办公区域时多见,此时应其设置。C.探测器至墙壁、梁边的水平距离,不应小于0.5m;探测器周围0.5m内,不应有遮挡物。D.办公的房间或公共走到被货架、设备或隔断等分隔,其顶部至顶棚或梁的距离小于房间净高的5%时,每个被隔开的部分至少应安装一只探测器。E.探测器至空调送风口边的水平距离不应小于1.5m,并宜接近回风口安装。探测器至多孔送风顶棚孔口的水平距离不应小于0.5m。F.探测器宜水平安装。当倾斜安装时,倾斜角不应大于45º。光电感烟探测器的安装图:93、手动报警按钮、紧急启、停按钮的安装A.手动报警按钮,紧急启、停按钮应安装在墙上距地面或楼面高度1.5m。B.手动报警按钮,紧急启、停按钮应安装牢固,并不得倾斜。C.手动报警按钮、紧急启、停按钮外接导线,应留有不小于10cm的余量,且其端部应有明显的标志。4、各类模块的安装:A.在安装时一定要认清其型号,被控制的设备,被控制设备所能提供的接点及接线方式,达到的要求等。B.模块一定要固定牢固,安装于被控制的设备的附近。C.模块的接线及保护措施要得当。5、接地问题:A、火灾自动报警系统接地装置的接地电阻值应符合下列要求:采用专用接地装置时,接地电阻值不应大于4Ω;采用共用接地装置时,接地电阻值不应大于1Ω。B、接地干线应采用铜芯绝缘导线,其线芯截面面积不应小于25m㎡。接地干线宜穿硬质塑料管埋设至接地体。C、由消防控制室接地板引至各消防电子设备的专用接地线应选用铜芯绝缘导线,其线芯截面面积不应小于4m㎡。10D、消防电子设备凡采用交流供电时,设备金属外壳和金属支架等应作保护接地,接地线应与电气保护接地干线(PE线)相连接。6、系统其它要求:A.消防控制设备的控制电源及信号回路电压宜采用直流24V。B.火灾自动报警系统应设有主电源和直流备用电源。C.火灾自动报警系统的主电源应采用消防电源,直流备用电源宜采用火灾报警控制器的专用蓄电池或集中设置的蓄电池。当直流备用电源采用消防系统集中设置的蓄电池时,火灾报警控制器应采用单独的供电回路,并应保证在消防系统处于最大负载状态下不影响报警控制器的正常工作。7、技术规范投标方保证整个系统完全符合所有中华人民共和国有关条例和规范,能满足招标文件的全部要求。(二)气体灭火系统工程七氟丙烷(无管网)灭火系统1、设计依据:1.《建筑设计防火规范》(GB50016—2006)2.《气体灭火系统设计规范》(GB50370—2005)3.《气体灭火系统施工及验收规范》(GB50263—2007)4.防护区尺寸2、防护区的概况:依据设计规范及用户要求并结合防护区的建筑特点,将防护11区设计为七氟丙烷无管网灭火系统,具体情况如下:序号防护区名称防护区体积(m3)设计用量(Kg)钢瓶容积(L)每瓶充装量(Kg)所需瓶数1机房214140707023、对防护区的设计要求:1.防护区内环境温度不低于-100C2.防护区内的通风机和通风管道中的防火阀,在喷放七氟丙烷药剂前应自动关闭;3.防护区应封闭良好4.防护区的隔墙和门的耐火极限均不应低于0.5h,吊顶的耐火极限不应低于0.25h,防护区的门应采用向疏散方向开启的自由门5.防护区内应有保证人员在30s内疏散的通道和出口,并设事故照明和疏散指示标志4、系统操作及控制方式:七氟丙烷无管网灭火装置具有自动、手动两种启动方式:1.防护区和消防控制均无人时采用自动控制,由两种火灾探测器同时探测出火灾信号,通过灭火控制器自动启动灭火系统进行灭火。2.当有人值班或防护区内有人工作时,应采用手动操作,人员发现火灾后,按动防护区外的启动按钮,通过灭火控制器自动启动系统进行灭火。这两种启动方式在喷射药剂前均有一段延时,并发出12警报。5、七氟丙烷灭火系统主要设计参数:1.设计灭火浓度:8%2.灭火剂喷射时间:不大于10s3.灭火剂贮压:2.5Mpa4.设计计算环境温度:200C六、重要部位质量通病及防治办法:(一)火灾自动报警及消防联动控制系统1.施工中管线敷设有断头、少线、接地、短路时应采取以下措施防冶:(1)施工前认真进行图纸会审和技术交底。明确报警布点位