、设计基础材料1.机加车间符合全部为三级负荷,对供电可靠性要求不高。2.车间平面布置图如下图所示。101112141315165678917181234262728293031323334192122242023低压配电室变压器室高压室车间变电所3.车间电气设备各细表如下表所示转供负荷名称计算负荷转供距离P30(kW)Q30(kvar)S(kV.A)I30(A)Cosφ金工车间回路130203654.90.83250回路2303445.368.90.66回路3404459.590.30.67合计10098402130.71汽车修理车间回路1302539.159.30.77100回路2222533.350.60.67回路3303646.971.20.65合计82861191810.69备品车间回路128304162.30.68150回路2192531.447.70.60回路3354053.280.80.66合计82951251890.61锅炉房回路1233037.857.40.65200回路2172026.239.90.45回路3153033.550.960.57合计558097.1147.51.0照明回路(3相)回路11701725.81.0200回路21201218.21.0回路31601624.31.0合计4504568.41.04.车间低压母线专供负荷如下表所示。设计题目序号总降压变电所车间变电所地区环境最热日平均气温(℃)车间最大负荷利用小时数Tmax(h)土壤情况自然接地电阻(Ω)二次母线短路容量(MV.A)保护动作时限tp(s)电源进线电压(kV)电阻率Ω.m导线类型U1NU2NSk.maxSk.min长度l(km)架空电缆地上地下12001501.20.4√100.4302845001002022502001.30.4√100.4352055001006031801501.00.6√100.4252335003001543002501.10.5√60.4353340004002552001501.21.8√100.4272545003001264003501.02.0√100.430275500501077502001.31.5√100.4323060002003083503001.12.5√60.42523550060185.车间采用三班制。年最大有功负荷利用小时数为5500H。6.供电电源条件:从本厂35/10KV总降变电所用架空线引进10KV电源,该变电所距本车间南0.3KM。电路系统短路数据见表3。供电部门提出的技术要求如下:工厂总降压变电所10KV配电出线定时限过电流保护装置的整定时间tp=1.3s。车间最大负荷时功率因数不得低于0.9。在车间变电所10KV侧进行计量。供电贴费为700元/(KV.A),每月电费按两部电价制:基本电费为18元/(KV.A),动力电费为0.4元/(Kw.h),照明电费为0.5元/(Kw.h)。7.工厂自然条件。气象条件。年最高气温38度,年平均气温35度,年最低气温8度,年最热月平均最高温30度,年最热月地下0.7米-1米处平均温度20度,常年主导风向为南风;年雷暴日180天;土壤冻结深度1.1米。地质水文资料。平均海拔200米,地层以沙质黏土为主,地下水位3米-5米,地耐压力位20吨每平方米。三、基本要求(1)说明书要简明扼要,计算要有公式依据,结果要列表记人,必要的数据及资料要注明出处。提倡用计算机绘图和打印设计说明书。(2)设计图样要符合国家标准,采用新标准电气图形符号和文字符号,图样上的字必须用仿宋体。(4)要列出参考书目(文献)。(5)要有设计结论(或总结或体会)。四、主要技术指标机加车间符合全部为三级负荷,对供电电源无特殊要求;用需要系数法计算出各种车间的计算负荷,然后计算出多组用电设备的计算负荷,然后通过功率因数计算出年耗电量;车间变电所宜采用一台变压器。五、应收集的资料及参考文献[1]刘介才.工厂供电[M].北京:机械工业出版社,2003[2]供配电系统设计规范[M].北京中国计划出版社,1996[3]电气工程师手册(第二版)机械工业出版社