D2G4是日本系统的安全规格规格如下:Protectionmethods:d=flameproof(sameconceptasinIEC60079-1,1990)e=increasedsafety(sameconceptasinIEC60079-7,1990)i=intrinsicsafety(sameconceptasinIEC60079-11,1991)o=oilimmersion(sameconceptasinIEC60079-6,1968)p=pressurization(sameconceptasinIEC60079-2,1983)Note-Theprotectionmethods:'m','q',and'n',havenotyetbeenadoptedbytheMHLW,andthereforearenotavailableasacertificationoptionthroughTIIS.Explosiongrades(GasgroupsinIEC):1=propane(sameasIIAinIEC)2=ethylene(sameasIIBinIEC)3a=hydrogen(sameasIIB+H2inIEC)3b=carbondisulfide(IIB+CS2inIEC)3c=acetylene(IIB+C2H2inIEC)3n=allthegasesingrade3(sameasIICinIEC)Ignitioncategories(TemperaturecodesinIEC):G1=450°C(sameasT1inIEC)×0.8-40°C=320°CriseG2=300°C(sameasT2inIEC)×0.8-40°C=200°CriseG3=200°C(sameasT3inIEC)×0.8-40°C=120°CriseG4=135°C(sameasT4inIEC)×0.8-40°C=68°CriseG5=100°C(sameasT5inIEC)×0.8-40°C=40°CriseG6=85°C(sameasT6inIEC)×0.8-40°C=28°Crise以下则是国标定义dⅡBT4d代表隔爆型,此项代表爆炸性气体环境电气设备的选型,即在爆炸性气体区域(0区、1区、2区)不同电气设备使用安全级别的划分。如旋转电机选型分为隔爆型(代号d)、正压型(p)、增安型(e)、无火花型(n);灯具类选型分为隔爆型(代号d)、增安型(e);信号、报警装置选型分为本质安全型(ia、ib)、隔爆型(代号d)、增安型(e)。ⅡB代表气体或蒸气爆炸性混合物等级的划分,分为ⅡA、ⅡB、ⅡC三种,其中ⅡA最低(如通常的烷烃甲烷乙烷;芳香烃苯、甲苯),ⅡB类主要有丙炔、乙烯、环丙烷、1,2-环氧丙烷、焦炉煤气等;ⅡC最高(主要有氢、乙炔、二硫化碳、硝酸乙酯、水煤气等。这些等级的划分主要是依照最大试验安全间隙(MESG)或最小点燃电流(MICR)来区分的。T4代表135<T≤200℃,它的定义是指能引燃某种介质的温度分组的划分。主要分为T1——450℃<T、T2——300<T≤450℃、T3——200<T≤300℃、T4——135<T≤200℃、T5——100<T≤135、T6——85<T≤100℃.