摘要本文主要针对当前供水系统中存在的自动化程度不高、能耗严重、可靠性低的缺点加以研究,设计出一种在这三个方面都有所提高的PLC控制的恒压供水系统。恒压变频供水系统是当今应用最广泛的节能型供水系统。本文通过对供水系统运行特征及工作状态的分析,阐述了系统的节能原理,介绍了系统的基本构成及特点。并从实际出发,通过对PLC,变频器,离心水泵等原理的介绍,阐述了整个系统实现的理论基础,通过具体编制PLC程序,实现了控制要求,较好的满足了工艺要求。本文所做的研究对同类系统的研究和再开发具有一定的参考价值。关键词:变频调速;节能;PLC控制2AbstractInthispaper,thewatersupplysystemforthecurrentdegreeofautomationthatexistinlowenergyconsumptionandseriousdefectsofthelowreliabilityoftheresearch,designakindofthreeareasinwhichthePLChastoincreasethecontrolofconstantpressurewatersupplysystem.Constantpressurewatersupplysystemfrequencyisthemostwidelyusedenergy-efficientwatersupplysystem.Inthispaper,thecharacteristicsofthewatersupplysystemoperationandanalysisofthestateonthesystem'senergy-savingprincipleofthesystem'sbasicstructureandcharacteristics.Andproceedfromreality,throughthePLC,frequencyconverter,theprincipleofcentrifugalwaterpumps,etc.,thewholesystemonthetheoreticalbasisforthepreparationofPLCthroughspecificprocedures,toachievethecontrolrequirements,thebettertomeetthetechnologicalrequirements.Inthispaper,theresearchdoneonsimilarsystemsintheresearchandfurtherdevelopmentofacertainreferencevalue.Keywords:FrequencyControl;EnergySaving;PLC热让他3目录1.恒压供水原理及工艺................................................................................................11.1任务.................................................................................................................11.2工艺要求.........................................................................................................11.3系统的组成和基本工作原理.........................................................................12PLC概述.....................................................................................................................32.1PLC组成........................................................................................................32.1.1PLC的输入..........................................................................................32.1.2PLC的输出........................................................................................32.1.3PLC的控制机制................................................................................33系统硬件设计............................................................................................................63.1恒压供水系统的基本构成...........................................................................83.2系统控制要求.............................................................................................103.3控制系统的I/O点及地址分配..................................................................103.4系统选型.....................................................................................................123.5PLC模拟量模拟量控制单元的配置以及应用..........................................123.5.1EM235模拟量工作单元性能指标..................................................133.5.2校准及配置.....................................................................................143.5.3EM235的安装使用..........................................................................143.5.4EM235工作程序编制......................................................................153.5.5电气控制系统原理图.....................................................................164.系统程序设计........................................................................................................194.1由“恒压“要求出发的工作泵组数量控制管理.......................................194.2多泵组泵站泵组管理规范............................................................................194.3程序的结果以及程序功能的实现...............................................................19参考文献......................................................................................................................32致谢..............................................................................................................................3411.恒压供水原理及工艺1.1任务随着社会的发展和进步,城市高层建筑的供水问题日益突出。一方面要求提高供水质量,不要因为压力的波动造成供水的障碍;另一方面要求保障供水的可靠性和安全性,在发生火灾时能可靠供水。针对这两方面的要求,新的供水方式和控制系统应运而生,这就是PLC控制的恒压无塔供水系统。恒压无塔供水系统包括生活用水的恒压控制和消防用水的恒压控制——即双恒压系统。恒压供水保证了供水的质量,以PLC为主机的控制系统丰富了系统的控制功能,提高了系统的可靠性。1.2工艺要求对三泵生活/消防双恒压供水系统的基本要求是:(1)生活供水时,系统应底恒压值运行,消防供水时系统应高恒压值运行。(2)三台泵根据恒压的需要,采用“先开先停”的原则介入和退出。(3)在用水量小的情况下,如果一台泵连续运行的时间超过3H,则要切换到下一台泵,即系统具有“倒泵功能”,避免某一台泵工作时间过长。(4)三台泵在启动时要有软启动功能。1.3系统的组成和基本工作原理以一个三泵生活/消防双恒压无塔供水系统为例来说明其工艺过程,市网来水用高低水位控制器EQ来控制注水阀TV1,它们自动把水注满储水池,只要水位低于高水位,则自动往水箱中注水。水池的高/低水位信号也直接送给PLC,作为低水位报警用。为了保障供水的持续性,水位上下限传感器高低距离不是相差很大。生活用水和消防用水共用三台泵,平时电磁阀YV2处于失电状态,关2闭消防管网,三台泵根据生活用水的多少,按一定的控制逻辑运行,使生活用水的恒压状态(生活用水底恒压值)下进行;当有火灾发生时,电磁阀YV2得电,关闭生活用水管网,三台泵共消防用水使用,并根据用水量的大小,使消防供水也在恒压状态(消防用水高恒压值)下进行。火灾结束后三台泵再改为生活供水使用。32PLC概述2.1PLC组成2.1.1PLC的输入通过对继电器控制特点的介绍和最初通用汽车公司提出的要求分析。PLC要想取代继电器控制,首先要解决外部设备的直接输入问题。由于当时主要集中在开关量控制,也就是开关量(触点的开闭状态)如何直接接入PLC并被PLC所识别,对此就需要解决以下几个问题:有源接入,无源接入,绝缘问题,隔离问题和互相干扰问题。PLC就是一个计算机控制系统,在其发展过程,人们曾将计算机直接用于工业控制,但是由于以下两大问题没有解决好而难以发展:一是I/O(输入/输出)问题,计算机不能直接和工业现场设备连接现在了应用;二是计算机的I/O功能,开关逻辑处理不够丰富和强大。现在的PLC成功的解决了这两个方面的问题,可以让PLC和外部设备直接进行物理的连接。计算机的内部提供了丰富的从位逻辑到双字运算的强大的运算功能,使其能够完成复杂的控制功能,这也是PLC能够迅速发展的原因。2.1.2PLC的输出输出问题主要是接点的驱动能力问题,或者说是带负载能力和输出方式的问题。输出动作次数的限制,是保证PLC的输出接点能否驱动接触器、电磁阀这样的控制执行元器件的问题至少要能直接驱动中间继电器。现