牵引变电所常见故障判断及处理方案

整理文档很辛苦,赏杯茶钱您下走!

免费阅读已结束,点击下载阅读编辑剩下 ...

阅读已结束,您可以下载文档离线阅读编辑

资源描述

目录中文摘要··················································Ⅰ第1章绪论···········································11.1配电网供电可靠性分析和现状························11.2本文研究的意义及所完成的主要工作··················2第2章配电网元件概述及可靠性分析·························32.1元件可靠性的基本概念······························32.1.1可修复元件的状态····························32.1.2可修复元件的与失效有关的可靠性指标··········42.1.3可修复元件的与维修有关的可靠性指标··········52.1.4两种典型的元件寿命概率分布··················62.1.5元件的可用度································82.2配电网络元件的故障率分析··························92.2.1元件的故障率计算····························92.2.2元件组的故障率分析··························9第3章配电网可靠性计算方法······························11第4章10KV配电网供电可靠性分析···························134.1故障停电原因及对策·······························134.1.1外力破坏···································134.1.2自然灾害···································144.l.3高压用户影响·······························144.1.4导线问题···································144.1.5其他方面··································154.2非故障停电原因及解决办法·························154.2.1非故障停电原因·····························154.2.2解决办法··································15牵引变电所常见故障判断及处理方案第一部分牵引变电所处理故障的原则1、牵引变电所的故障处理及事故抢修,要遵循“先通后复”的原则。2、对于有备用设备的牵引变电所,首先要考虑投入备用设备,以最快的速度设法先行恢复供电,并采用正确、可行的方案,迅速、果断地进行事故处理和抢修。然后及时通知有关部门,再修复或更换故障设备。3、限制事故、故障的发展,消除事故、故障根源以及对人身设备的威胁。4、在危及人身安全或设备安全的紧急情况下,值班人员可以先行断开有关的断路器和隔离开关,然后再报告段调度。5、对于事故抢修,情况紧急时可以不开工作票,但应向段调度报告概况,听从段调度的指挥,在作业前必须按规定做好安全措施,并将抢修作业的时间、地点、内容及批准人的姓名等记录到值班日志中。6、事故抢修时,牵引变电所所长或负责人应尽快赶到现场担任事故抢修工作领导人,如果所长不在即由当班值班人负责人自动担任抢修领导工作。第二部分牵引变电所事故抢修一般规定1、牵引变电所中发生电气设备事故(故障)后,值班员应迅速报告段调度,除按规定收集故障信息进行现场防护外,还应在力所能及的范围内采取措施,防止事故的发展,尽可能消除事故根源,减少事故损失。在危及人身安全或设备安全的紧急情况下,值班人员可先行断开有关的断路器和隔离开关,然后再报告供电调度。2、事故抢修时,可不开工作票,但必须有段调度的命令,并按规定做好安全措施。事故抢修时,有上级领导在现场,由上级领导择人担当工作领导人;无上级领导在现场时,由变电所所长担任抢修工作领导人。抢修时要有明确的分工,并指定专人负责与供电调度保持联系。3、牵引变电所发生事故后,段机关指挥中心成员及变电系统值班人员必须到生产调度协助指挥抢修,各级领导及有关技术人员了解现场情况时,应派专人通过自动电话联系,下达指示时应通过供电调度指挥电话进行,以免造成混乱。4、变电所所长及每一位值班人员都应熟悉牵引变电所事故抢修、抢险预案,每月至少组织进行一次事故抢修演练。5、牵引变电所所长在遇有大降暴雨等恶劣天气时,应立即设法以最短的时间赶赴变电所,组织并参加防洪抢险工作。6、所有的抢修、防洪储备料具齐全,随时处于良好状态。防洪期间,变电所应将防洪料具检查纳入每次交接班中。各供电车间、技术科每月检查一次,段每季组织检查一次。7、抢修、防洪料具严禁外借。抢修、防洪料具在使用后,要及时上报补充计划,由段物资部门予以补充和追加。第三部分故障判断的方法及步骤1、方法一般情况下,要依据仪表指示、灯光显示、事故报告单,以及设备巡视、外观等情况,进行综合分析。2、步骤①.依据断路器的位置指示灯,找出跳闸的断路器。②.依据保护装置面板显示,光字牌指示、事故报告单以及信号继电器的掉牌找出是哪台设备的哪套保护动作。③.依据故障报告单及继电保护范围,判断出故障范围和明确故障地点。④.依据现场设备外观检查情况,确定故障设备是否需要退出,如果需要退出,可以申请投入备用设备或改变现行的运行方式。四、常见故障处理方案(一)高压室内故障1、进线穿墙套管闪络或击穿如果进线穿墙套管闪络或击穿,首先向段调度汇报,并申请倒主变,尽快恢复供电。送电后对主变高、低压侧断路器立即进行检查及保护校验,等有天窗点再对进线穿墙套管进行更换。2、27.5kv电压表指示摆动时的应急措施在正常运行中,如果值班人员发现27.5kv电压表指示低于正常值很多或出现忽高忽低时,主要由该电压互感器一次高压熔断器所熔断引起。值班人员应及时向段调度进行汇报,投入备用电压互感器,然后撤除故障电压互感器,在保证人身设备安全的情况下进行检查更换该电压互感器的高压熔断器。3、动力变穿墙套管闪络或击穿3.1穿墙套管闪络或击穿,应将相应的装置退出运行,拉出小车,先行恢复供电;送电后对该装置断路器重点检查及保护校验,等有天窗点再对穿墙套管进行更换。3.2动力变穿墙套管闪络或击穿,应将动力变退出运行,拉出小车,先行恢复供电;送电后应立即对动力变断路器重点检查及保护校验,等有天窗点再对穿墙套管进行更换。同时改变现有的供电方式,有贯通线的由贯通线供电,无贯通线的采取越区供电,确保正长供电。4、母线支持瓷瓶闪络或击穿4.1如果是母线支持瓷瓶表面发生轻微闪络,可采用强送一次,如果强送电成功,就可以正常投入设备运行。4.2如果强送一次后失败,那就说明瓷瓶发生严重闪络或击穿,在保证人身安全的前提下,用手锤将闪络或击穿的瓷瓶打掉后再送电,等有天窗点再对母线支持瓷瓶进行更换。5、隔离开关支持瓷瓶闪络或击穿5.1如果隔离开关支持瓷瓶闪络或击穿发生在负荷侧,直接将其相应的隔离开关拉开后,再投另一台电压互感器或备用变,等有天窗点再对隔离开关支持瓷瓶进行更换。5.2如果发生在27.5kV母线侧,将该隔离开关拉开后,在保证人身设备安全的前提下,将其闪络或击穿的瓷瓶用手锤敲掉后,再投另一台电压互感器或备用变,等有天窗点再对隔离开关支持瓷瓶进行更换。5.3如果为母联开关,若1或2支持瓷瓶爆炸,将爆炸瓷柱用手锤敲掉,先行恢复送电;若3或4支持瓷瓶爆炸,拆除母联开关引线,用采用同型号的母线直接将母线短接,先行恢复送电。以上两种情况等有天窗点时,再进行对隔离开关支持瓷瓶进行更换。(二)110KV侧1、110Kv断路器拒动1.1如果是控制回路小保险熔断。更换同型号保险后,再次合闸。1.2如果备用开关不能投运,则应断开所有控制电源,手动合(分)圈铁心,进行合(分)闸。2、在“直接位”操作110Kv电动隔离开关拒动2.1若控制回路小保险熔断。更换同型号保险后,再次合闸(分闸)。2.2若控制回路小保险未熔断,在隔离开关机构箱内进行“当地”操作。2.3若“当地”操作不成功,用摇把手动操作。3、110Kv断路器不能储能3.1在机构箱内按下储能控制继电器,进行储能。3.2如果电机不转,则应将手动或电动连锁开关打至手动储能位置,用储能专用手柄进行手动储能。4、110kv线路失压4.1如果有电压监测装置的变电所,观察另一回路是否有电,如果有电应立即建议段调度切换到另一回路。4.2如果有无电压监测装置的变电所,应立即在另一回路验电,如有电应立即建议段调度切换到另一回路。4.3如果有线路备自投装置的变电所,失压后备自投装置启动,监测有电后向段调度报告。5、110kv断路器气体泄漏低于规定值5.1当发出“气体压力过低警告”光字牌时,值班员要时刻监视设备运行并及时向段调度汇报。5.2当发出“气体压力过低闭锁”光字牌时,及时向段调度报告并且值班人员应采取下列方法进行处理:①.如果该设备处于热备状态,值班人员立即先将断路器退出热备,并悬挂禁止合闸标示牌,尽快由检修人员进行检修补气。②.如果该设备处于运行状态,值班人员立即申请倒换主变,用隔离开关将断路器及主变撤除运行。6、110KV少油断路器故障应急措施液压操作机构压力降低,油泵频繁打压。如果发生这种情况,应立即向供电调度汇报,并申请倒主变。(三)馈线侧1、馈线侧穿墙套管闪络或者击穿1.1如果是瓷瓶表面发生轻微闪络,可强送一次,如果强送电成功,就可以正常投入设备运行。1.2如果强送一次后失败,那就说明穿墙套管发生严重闪络或击穿,在保证人身安全的前提下,等有天窗点时再对馈线侧穿墙套管进行更换。1.3申请采取越区供电方式。2、馈线断路器故障应急措施2.1馈线断路器远动操作拒合①.值班人员应先检查直流系统,看该电压是否正常,绝缘是否良好,有无接地现象。②.值班员向段调度申请将控制盘上位置转换开关打至“当地位”,在控制盘上手动操作控制开关进行合闸操作;或者值班员向段调度申请将控制盘上位置转换开关打至“就地位”,在断路器本体上将位置转换开关打至“当地位”,手按合闸按钮进行合闸。③.如果上述操作仍合不上闸,值班员向段调度申请投入备用断路器。④.恢复送电后,应巡视设备,并将有关情况做好记录并向段调度汇报相关情况。2.2馈线断路器远动操作拒分①.值班人员应先检查直流系统,看其电压是否正常,绝缘是否良好,有无接地现象。②.值班员向段调度申请将控制盘上位置转换开关打至“直接位”,在控制盘上手动操作控制开关进行分闸操作。③.如果上述操作仍不能分闸,并且操作过程中出现“控制回路断线”光字牌,值班员应向段调度申请将控制盘上位置转换开关打至“单独位”,在断路器本体上将位置转换开关打至“当地位”,手按分闸按钮进行分闸。④.如果上述操作还不能分闸,手动操作断路器“紧急分闸”按钮进行分闸。⑤.值班员向段调度申请投入备用断路器;并将有关情况做好记录并向段调度汇报相关情况。2.3馈线断路器出现故障时,投运备用断路器是首选的最快捷方案。如果馈线在送电时,电动合不上主断路器,而备用断路器又在检修时,应进行下面处理:①.断开主变相应的次边断路器;②.手动合上馈线断路器;③.用主变次边断路器代替馈线送电;④.尽快恢复备用断路器。2.4馈线断路器越级跳闸处理①.应先观察母线是否出现低电压,馈线是否出现大电流,低电压保护是否出口;②.如果低电压保护没有出口,则说明馈线断路器有问题,必须倒馈线断路器,停用运故障馈线断路器;③.如果主用断路器,备用断路器同时出现问题,则手动强行合上其中的任何一个断路器。3、馈线断路器3.1馈线断路器自动跳闸且重合成功①.解除事故音响,记录跳闸时间;②.找出掉找的断路器,及各种信号;③.查看事故报告单并复归信号;④.计算、查找故障点的位置;⑤.巡视相关设备,并将有关情况做好记录;⑥.按有关规定及时向段调度汇报跳闸情况。3.2馈线开关自动跳闸且重合失败①.解

1 / 27
下载文档,编辑使用

©2015-2020 m.777doc.com 三七文档.

备案号:鲁ICP备2024069028号-1 客服联系 QQ:2149211541

×
保存成功