金山桥热电厂3×220t/h锅炉异地扩建工程电动给水泵技术规范书徐州金山桥热电有限公司中机电力工程有限公司2010.10上海目录1总则··············································································12设备使用条件及环境·························································13设备规范········································································44技术要求········································································75供货范围······································································176质量保证及试验·····························································187监造及验收···································································218包装、运输···································································239技术资料······································································2410交货进度····································································2511技术服务和联络·····························································26金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书1总则1.1本规范书适用于金山桥热电厂3×220t/h锅炉异地扩建工程的给水泵。该设备的功能设计、结构、性能、安装和试验等方面均应满足相应的技术要求。1.2本规范书提出的是最低限度的要求,并未对一切技术要求作出详细规定,也未充分引述有关标准及规范的条文。供方应保证提供符合本规范书和相关的最新的国家和行业标准并有两台以上成功业绩的优质产品。1.3本规范书所引用的标准若与供方所执行的标准发生矛盾时,按较高的标准执行。1.4供方对锅炉给水泵组的成套系统设备(含辅助系统与设备)负全责,即包括分包(或采购)的产品。分包(或采购)的产品制造商应事先征得需方的认可。1.5在合同签定后,需方有权因规范、标准、规程发生变化而提出一些补充要求。2设备使用条件及环境2.1设备的运行环境条件建设地址:徐州三环北路以南,黄石路以北,京沪铁路以东,徐州中能硅业科技发展有限公司以北的地块。气象条件:气压:历年平均气压:101.220kPa历年年最高气压:104.240kPa(2000年1月31日)年平均雷暴日数25.5天气温(℃):历年平均气温:14.4极端最高气温:40.6(1972年6月11日)极端最低气温:-22.6(1969年2月6日)历年平均最高气温:19.8历年平均最低气温:9.9历年最热月平均气温:27.1(7月)历年最冷月平均气温:0.2(1月)金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书历年最热月最高气温平均:34.0(1994年7月)相对湿度(%):历年平均相对湿度:69最小相对湿度:2(1961年2月19日、1965年3月15日)降水量(mm):历年平均降水量:842.5历年最大年降水量:1213.4(1963年)历年最大月降水量:481.3(1982年7月)历年最大一日降水量:315.4(1997年7月17日)历年最大一小时降水量:83.5(1997年7月17日)历年最长一次降水量:368.8(1965年7月6--22日)蒸发量(mm):历年平均蒸发量:1798.9历年最大蒸发量:2279.0(1978年)风:历年平均风速:2.6m/s实测10分钟平均最大风速:15.8m/s(SSW)全年主导风向:ENE(频率12%)夏季主导风向:ENE、E、ESE(频率11%)冬季主导风向:ENE(频率13%)积雪:累年最大积雪深度为27cm,发生于1991年3月27日,日积极端最大雪深度13cm。最大冻土深度:24cm(1968年1月2日)地震烈度及厂址标高:按抗震设防烈度为7度考虑。基本地震加速度0.10g金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书厂址标高:m(海拔)2.2主机设备参数型式:循环流化床锅炉,3台铭牌出力:220t/h额定出力:260t/h过热蒸汽压力(表压):9.8Mpa过热蒸汽温度:540℃给水温度:150℃2.3除氧器参数除氧器3台,定压运行。除氧器出力:286t/h除氧器正常运行压力:0.59MPa(a)除氧器正常运行水温:158℃除氧器层标高:16.5m(以主厂房0m为基准)2.4给水泵入口给水水质输送介质名称:锅炉给水。名称单位给水总硬度μmol/L/溶氧μg/L≤7PH值(25℃)8.8~9.3铁μg/L≤30铜μg/L≤5钠μg/L/二氧化硅μg/L≤20联氨μg/L≤500氢电导率(25°C)μS/cm≤0.3金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书2.5设备安装位置本工程扩建三台220t/h高压、高温循环流化床锅炉,并预留2台B15MW背压机组的扩建场地,不设高、低加给水回热加热系统。从除氧器出来的给水经给水泵加压后直接进入锅炉省煤器。主厂房按汽机房、除氧煤仓间、锅炉房布置,除氧煤仓间、锅炉房本期建设,汽机房位置预留,给水泵布置在预留的汽机房内零米位置,靠近除氧煤仓间的位置建一个披屋做为给水泵房。2.6.给水泵数量及型式本期工程配4台100%容量给水泵,其中3台为电动定速给水泵,1台为液力耦合器调速电动给水泵,电动机、液力耦合器及给水泵同轴。每台给水泵设一个稀油站,稀油站布置在给水泵旁边。电动机电源电压:高压10.5kV;低压380V。2.7给水泵的运行方式在锅炉正常运行工况下,2台电动定速给水泵及1台调速给水泵运行,每台给水泵满足锅炉负荷要求,并根据锅炉负荷调整给水量。在锅炉启动状态下,给水泵调速运行时,并通过锅炉给水调节阀组调节锅炉给水量。3设备规范3.1给水泵的设计参数(供方填写)项目单位运行工况额定工况(保证效率)最大运行(设计)工况泵型号进水温度℃150150进水压力MPa(g)进水流量t/h260300抽头压力MPa(g)抽头流量t/h出口压力MPa(g)13.1出口流量t/h260300效率%≥80必需汽蚀余量m≤4金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书密封型式机械密封转速r/min轴功率kW轴振(双振幅)mm接口法兰公称压力进口MPa(g)抽头MPa(g)出口MPa(g)接口管子规格(φ×S)进口mm抽头mm出口mm重量kg旋转方向时针(从向看)轴承型式注:表中(g)系指表压。3.2电动机参数(供方填写)项目单位数值型号额定功率kW额定电压kV同步转速/额定转速r/min频率Hz主要特性效率%功率因数增转转矩(倍)堵转电流(倍)最大转矩(倍)绝缘等级重量kg冷却方式旋转方向时针(从向看)3.3液力耦合器技术数据(供方填写)项目单位数值型号输入转速r/min额定输出转速r/min额定输出功率kW重量kg调速范围%金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书额定滑差%输出轴旋转方向时针(从向看)3.4水泵接管附加位移(供方填写)(单位:mm)泵名称进口方位出口方位抽头方位给水泵xyz3.5水泵管接口允许承受的力和力矩(供方填写)泵名称力(N)力矩(N-m)进口出口进口出口给水泵xyz3.6主要零部件的材料(1)给水泵主要零部件的材料(供方填写)零件名称材料名称标准代号外壳体泵盖吸入段(单壳体)吐出段(单壳体)吸入接管吐出接管中段或内壳体吸入段导叶末级导叶叶轮轴平衡盘(鼓)平衡套壳体密封环中间衬套双头螺栓穿杠轴承支架金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书(2)液力耦合器主要部件材料(供方填写)零件名称材料名称标准代号壳体轴涡轮和涡轮套勺管调速齿轮4技术要求供方所提供的给水泵组必须是技术先进,经济合理,成熟可靠的产品,并具有较高的灵活性,既能够满足锅炉运行方式的需要,也能适应锅炉启停与变负荷的要求。4.1给水泵的特性曲线4.1.1给水泵组的流量与扬程的关系曲线应是无驼峰的运行稳定曲线,从额定流量到零流量的扬程应是稳定上升的,其扬程升高值应不超过额定流量时扬程的25%。4.1.2电动给水泵组并联运行时,泵组的特性曲线在调速范围内相互协调,以便泵组并联运行。如果一台电动给水泵发生故障,备用给水泵组能在30秒内投运点达到所需压力。4.1.3给水泵组能在最大运行点下长期连续运行,并作为泵的最大设计点,可不考虑超越。4.1.4给水泵在经常运行工况下,使其运行效率处于最高效率点,在额定工况、最大工况下运行时,给水泵的流量、扬程、效率及液力耦合器的滑差输出转速变化范围等性能都能予以保证,符合GB3216的规定。4.2给水泵组的综合性能4.2.1在任何允许运行工况下均保证给水泵不会发生汽蚀。在并列运行中一台泵停运时,其他泵在额定转数下连续运行,不发生汽蚀。4.2.2泵的自动再循环系统(泵保护阀)控制最小流量不超过额定流量的25%,具有流量测量、减压控制、止回阀的综合功能。泵的最小流量不超过额定流量的20%~25%,最小流量调节装置与水泵流量匹配,具有连续调节的性能。4.2.3在作最小流量再循环工况运行时,电动给水泵组应能承受液力耦合器最大转速要求。4.2.4最小流量调节装置后的压力不超过0.8MPa。最小流量阀有瞬间提升阀门30%开度的特性,以尽量减少阀芯与阀座的损坏。给水泵最小流量控制纳入DCS,并提供控制要金山桥热电厂3×220t/h锅炉异地扩建工程给水泵技术规范书求及SAMA图。4.2.5泵的临界转速:对于刚性转子,泵的第一临界转速不应低于最大工作转速的125%。对于挠性转子,泵的工作转速(n)应大于第一临界转速(n1)而小于第二临界转速(n2),其范围为:1.4n1n0.7n2泵不在正常运行范围内的任何转速下发生异常振动。4.2.6泵的转子及其主要的旋转部件都应进行静平衡和动平衡试验。静平衡精度不低于GB9239中的G6.3级,动平衡精度不低于GB9239中的G2.5级。泵的振动在无汽蚀运转条件下测量,轴承处的振动值符合JB/T8097的规定。给水泵轴承座振动双振幅值不大于0.038mm。4.2.7噪声控制标准:主给水泵、前置泵及液力耦合器应符合JB/T8098及DL5053-1996中的有关规定“即距泵体外壁1米、距地面高(泵高+1)/2米处的噪声不大于85dB(A)。”(给水泵配有本体保温罩,设备整体保证满足本条所述的噪音要求,填充材料符合环保要求。)4.2.8给水泵的结构强度考虑地震力的影响。4.3给水泵组成套设计要求4.3.1泵组成套设计由供方负责,并向需方提供完整的泵组资料。4.3.2供方成套的设计内容4.3.2.1电动给水泵组的油系统、冷却水系统应进行统一规划和布置,标明系统中各设备、阀门、管道及有关部件的供货界线。4.3.2.2配套提供电动给水泵组的热控仪表,提出其热工保护及联锁要求,并列出供货范围、设备清单等。4.3.2.3电动给水泵组外不安装隔音罩。4.3.2.4给水泵的进口管上分别装设可拆滤网。滤网的阻力应尽可能小,滤网随厂家成套供货。4.3.2.5给水泵的出口逆止阀及最小流量控制装置随厂家成套供货。4.3.2.6采用全抽芯的筒式双壳体结构(芯包