1目录1设计说明书·····················21.1设计依据························21.2设计概况························21.4设计范围························21.5设计成果························22设计说明书·····················32.1室内给水工程······················32.1.1系统选择及方案比较·······················32.1.2系统组成····························32.1.3加压设备及构筑物························32.2室内排水工程······················32.2.1系统选择····························32.2.2系统组成····························32.2.3排水管道布置与敷设······················42.3.1系统选择····························52.3.2系统组成····························52.3.3消火栓系统管网布置·······················62.3.4消火栓的布置原则························62.3.5消防水泵接合器·························73设计计算书·····················83.1给水设计计算······················83.1.1竖向分区···························83.1.2用水量标准及各区用水量计算··················83.1.3管网水力计算·························83.2消防设计计算······················153.2.1消火栓的选定·························153.2.2消火栓系统的组成·······················153.2.3贮水池的贮水容积计算·····················153.2.4消火栓系统的计算·······················153.3排水设计计算······················183.3.1排水系统选择························183.3.2系统中卫生器具当量表4-1···················183.3.3排水系统水力计算······················193.3.4排水管径的计算·······················21致谢························23主要参考文献····················2421设计说明书1.1设计依据《建筑给排水设计规范》GB50015—2003(2003年版)《高层民用建筑设计防火规范》GB50045—95《建筑设计防火规范》GBJ16—87《给水排水设计手册》第二册《建筑给水排水》第二版1.2设计概况该建筑为一栋普通高层住宅。查《建筑给排水设计规范》GB50015-2003知此建筑属于普通住宅Ⅱ类住宅,时变化系数取2.3。所处城市市政设施配套完善,地上15层,无地下层。总高为45m,分为3个单元。一到十五层平面图一样致,每个单元每层为六户。房间内设有沐浴器、浴盆、洗脸盆、低水箱坐式大大便器、洗涤盆。其中浴盆、洗脸盆、洗涤盆需热水供应。每户按4人计算。用水量按200L/人·d。1.4设计范围本次设计本专业设计内容具体主要包括室内生活给水系统,室内生活排水系统,消防系统管网布置。1.5设计成果1设计说明书、计算书2给水、排水、消防平面布置图一张3给水系统图一张4排水系统图一张5消防系统图一张6卫生间、厨房大样图一张32设计说明书2.1室内给水工程2.1.1系统选择及方案比较室外给水管网常年可用水头有0.35Mpa,可以考虑直接向较低的几层供水。经过方案的比较,室内给水系统采用分区供水方式,分为高、低二个区,高区(6-15层)采取上行下给供水方式,即市政管网——地下贮水池——水泵——屋顶水箱——高区各层用水点。低区(1-5层),采用下行上给供水方式,即市政管网直接供地区各用水点。2.1.2系统组成该建筑给水系统包括引入管﹑水表节点﹑给水管网和附件,此外,加压泵﹑屋顶高位水箱。2.1.3加压设备及构筑物加压泵采用两台。其中,一用一备。屋顶设生活给水水箱。2.2室内排水工程2.2.1系统选择因为该建筑所排出污水的污水性质、污染程度、结合室外排水系统体制,及所处城市市政设施比较完善,污水处理厂运行良好,所以采用污废水合流制排水系统。由于污水立管的水流流速大,而污水排出管的水流流速小,在立管底部管道内产生正压值,这个正压值能使靠近立管底部的卫生器具内的水封遭受迫坏,卫生器具内发生冒泡、满溢现象,严重影响使用。因此本设计采用了排水立管上设置专用通气管,情况大为改观,立管底部负压通过专用通气管而释放、平衡。2.2.2系统组成卫生器具、排水横支管、排水立管、排水横干管、通气管、排出管、检查井、清扫口。42.2.3排水管道布置与敷设1.布置与敷设的原则:(1)排水畅通,水力条件好;(2)使用安全可靠,不影响室内环境卫生;(3)总管线短,工程造价低;(4)占地面积小,美观;(5)施工安装、维护管理方便;(6)保护管道不受破坏。2.排水立管的布置与敷设:(1)立管应靠近排水量大,水中杂质多,最脏的排水点处。(2)立管不得穿过卧室、病房,也不宜靠近与卧室相邻的内墙。(3)立管宜靠近外墙,以减少埋地管长度,便于清通和维修。(4)立管应设检查口,其间距不大于10m,但底层和最高层必须设。平顶建筑物可用通气管顶口代替最高层的检查口。检查口中心至地面距离为1m,并应高于该层溢流水位最低的卫生器具上边缘0.15m。3.排水横支管的布置与敷设:(1)排水横支管不宜太长,尽量少转弯,一根支管连接的卫生器具不宜太多。(2)横支管不得穿过沉降缝、烟道、风道。(3)横支管不得布置在遇水易引起燃烧、爆炸或损坏的原料、产品和设备上面,也不得布置在食堂、饮食业的主副食操作烹调的上方。(4)横支管与楼板和墙应有一定距离,便于安装和维修。(5)当横支管悬吊在楼板下,接有2个及2个以上大便器或3个及3个以上卫生器具时,横支管顶端应升至上层地面设清扫口。4.排水横干管与排出管的布置与敷设:(1)排出管以最短的距离排出室外,尽量避免在室内转弯。(2)建筑层数为5~6层,并且排水立管仅设置伸顶通气管时,最低排水横支管与立管连接处距排水立管底垂直距离若小于0.75m,则底部横管需单独排出。(3)埋地管不得布置在可能受重物压坏处或穿越生产设备基础。(4)埋地管穿越承重墙或基础处,应预留洞口,且管顶上部净空不得小于建筑物的沉降量,一般不宜小于0.15m。5(5)湿陷性黄土地区的排出管应设在地沟内,并应设检漏井。(6)排出管与室外排水管连接处应设检查井,检查井中心到建筑物外墙的距离不宜小于3m。5.通气系统的布置与敷设:(1)生活污水和散发有害气体的生产污水管道应设伸顶通气管。(2)通气管需高出屋面不小于0.3m,但应大于积雪深度,上人屋面应大于2m。(3)连接4个及4个以上卫生器具,且长度大于12M的横支管和连接6个及6个以上大便器的横支管上要设环形通气管。(4)对卫生、安静要求高的建筑物内,生活污水管道宜设器具通气管。(5)器具通气管和环形通气管与通气管连接处应高于卫生器具上边缘0.15m,按不小于0.01的上升坡度与通气立管连接。(6)专用通气立管每隔2层,主通气管每隔8~10层设结合通气管与污水立管连接。结合通气管下端宜在污水横支管以下与污水立管以斜三通连接,上端可在卫生器具上边缘以上不小于0.15m处与通气立管以斜三通连接。(7)专用通气立管和主通气立管的上端可在最高层卫生器具上边缘或检查口以上不小于0.15m处与污水立管以斜三通连接,下端在最低污水横支管以下与污水立管以斜三通连接。(8)通气立管不得接纳污水、废水和雨水,通气管不得与通风管或烟道连接。2.3消防工程2.3.1系统选择据《建筑设计防火规范》8.6.2.3室内消火栓栓口处的静水压力应不超过80m水柱,如超过80m水柱时,应采取分区给水系统。消火栓栓口处的水压力超过50m水柱时,应设减压设施。所以根据实际情况,底层消火栓所承受的静水压力为43.5-1.1=42.4m80m,因此该消火栓系统可以不分区。屋顶设给水水箱,一旦发生火灾时先由生活水箱供水作为初期灭火之用。设消防水泵,作为后续灭火供水。2.3.2系统组成消防系统主要由消防泵,消防管网,消火栓,减压阀,水泵接合器组成。62.3.3消火栓系统管网布置1.室内管道布置成环状,环状管网的进水管的引入管成两条,当其中一根发生故障时另一只进水管保证消防用水量和水压的要求。2.保证同层相邻两个消火栓的充实水柱同时到达被保护范围内的任何部位,每根消防竖管的管径应按通过的流量计算确定,但不应小于100mm,以保证消防车通过水泵结合器向室内供水的可能性.3.高层建筑室内消防给水管网上应采用阀门分成若干独立段,已被检修.阀门的布置应使管道检修时关闭停用的立管不超过一条,消防管网阀门应经常处于开启状态,并应设有明显的起闭标志,信号火灾阀门开启后进行铅封.4.高层建筑室外设置水泵结合器,当室内消防水泵发生故障或遇大火室内消防水量不足时,供消防车从室外消火栓,消防储水池取水,通过水泵结合器将水送到室内消防给水管网.水泵结合器的设置数量按室内消防水量计算确定,采用两个,以利安全.5.水泵结合器应有明显的标志.并设在便于消防车使用的地点,其周围15--40m.范围内设置消防水池,水泵结合器本次设计采用地下式。2.3.4消火栓的布置原则消火栓的合理布置,直接关系到扑救火灾的效果。因此,高层建筑的各层包括和主体间相连的附属建筑均应合理设置消火栓。1.室内消火栓应布置在明显,易于取用的地方,严禁伪装消火栓。消防电梯前室应设消火栓。2.消火栓应保证同层相邻两个消火栓的水柱同时到达室内任何部位3.消火栓的水枪充实水柱长度应根据建筑物层高和选定的水枪设计流量通过水力计算确定。根据消防经验,对建筑高度不超过100m的高层建筑,充实水柱长度不应小于10m。4.消火栓口之径。高层建筑室内消火栓口之径应为65mm,水带长度不应超过25m,水枪喷嘴口径不应小于19mm。同一层建筑内,应采用同一型号,规格的消火栓和与其配套的水带及水枪5.消火栓口距地面的高度为1.1m,栓口出水方向宜向下或与设置消火栓的墙面垂直。76.高层建筑屋顶应设置一个装有压力显示装置的检验消火栓,以利于经常检查消火栓系统是否能正常运行,同时也可用于扑救相邻建筑的火灾,保护本建筑不受其火灾威胁。检验消火栓充实水柱为10m,水带长度为25m。冬季应在屋顶出口处,水箱间采取防冻措施。7.消火栓的间距应由计算确定,且高层建筑不应大于30m,裙房不应大于50m。8.当消火栓口处压力大于0.5Mpa时,应在消火栓处设减压阀装置,一般采用减压阀或减压孔板用以减少消火栓前的剩余水压,是消防水量合理分配,系均衡供水,利于节水和消防人员把握水枪安全操作,也可以避免高位水箱中的消防贮水量在短时间内用完。2.3.5消防水泵接合器水泵结合器是消防车往室内管网供水的接口。水泵结合器一端由室内消火栓给水管网最底层引至室外,另一端进口可供消防车或移动水泵站加压向室内管网供水。发生火灾时,如遇以下几种情况,均可采用消防车从室外消火栓取水,通过消防水泵接合器向室内消防给水管网供水:(1)室内消防水泵发生故障时;(2)室内遇大火,消防用水不足时;(3)室内消防用水不足,虽然消防水泵工作正常,但需向位于建筑物内的消防水池补充水。水泵接合器的设置位置:(1