122402GLOBALPLATFORMMANUALMONITORSTYLE3430INSTALLATION,OPERATINGANDMAINTENANCEINSTRUCTIONSThefollowingisintendedtoprovidethebasicinstructionsforinstallation,operatingandmaintenanceoftheGlobalPlatformManualMonitor.Readandunderstandtheseoperatinginstructionsbeforeuse.PRODUCTRATINGS:MaximumFlow:1000gpm(3800lpm)MaximumPressure:200psi(1400kpa)PRODUCTWARNINGS:Thereactionforcewhenflowingatthemaximumpressureandflowlistedaboveis750pounds.Thecenterofthewater-wayis103/16inchesfromthebottomoftheinletflange.Ensurethesevaluesplusanappropriatesafetyfactorareusedtodetermineapropersupportstructure.WARNING:INSUFFICIENTSTRUCTURALSUPPORTCANLEADTOFAILURE,WHICHHASPOTENTIALTOCAUSEANINJURY.THEREFORE,ADDITIONALSTRUCTURALSUPPORTATTHEINLETFLANGEMAYBEREQUIRED.NOSUPPORTSTRUCTUREISTOBEADDEDDIRECTLYTOTHEMONITOR.(ContactAkronBrassCustomerServiceforassistance.)WARNING:Chargetheunitslowly.Rapidchargingmaycauseapressuresurgewhichhasthepotentialtocauseaninjuryordamagethemonitor.WARNING:Aimtheunitinasafedirectionbeforepumpingwaterthroughit.WARNING:DONOTexceedthemaximumpressureorflowratingsofthemonitor.Exceedingtheseratingshasthepotentialtocauseaninjuryordamagethemonitor.WARNING:DONOTinstallshutoffsontheoutletofthemonitor.Shutoffsincreasethepotentialforpressuresurgesduetowaterhammer,whichhavethepotentialtocauseinjuryordamagethemonitor.WARNING:Drainthemonitorafterusetoprevent“freezedamage”.WARNING:Ensurethethreadonthenozzleswivelmatchesthethreadonthemonitoroutlet.Donotovertightenthenozzleontotheunit.MONITORATTACHMENT:Themonitoristobemountedonthewaterwaywitheight5/8inchboltsandnutsofgradefiveminimumandsuitablewasherswhenmountingtoaDIN80flange.Whenmountingtoathreeinchflange,onlyfourbolts,nutsandwashersarerequired.!!!!!!!ISO9001REGISTEREDCOMPANYPHONE:330.264.5678or800.228.1161IFAX:330.264.2944or800.531.7335I(5)yearsafterpurchaseagainstdefectsinmaterialsorworkmanship.AkronBrasswillrepairorreplaceproductwhichfailstosatisfythiswarranty.RepairorreplacementshallbeatthediscretionofAkronBrass.ProductsmustbepromptlyreturnedtoAkronBrassforwarrantyservice.Wewillnotberesponsiblefor:wearandtear;anyimproperinstallation,use,maintenanceorstorage;negligenceoftheowneroruser;repairormodificationafterdelivery;damage;failuretofollowourinstructionsorrecommendations;oranythingelsebeyondourcontrol.WEMAKENOWARRANTIES,EXPRESSORIMPLIED,OTHERTHANTHOSEINCLUDEDINTHISWARRANTYSTATEMENT,ANDWEDISCLAIMANYIMPLIEDWARRANTYOFMERCHANTABILITYORFITNESSFORANYPARTICULARPURPOSE.Further,wewillnotberesponsibleforanyconsequential,incidentalorindirectdamages(including,butnotlimitedto,anylossofprofits)fromanycausewhatsoever.Nopersonhasauthoritytochangethiswarranty.©PremierFarnellCorporation.2010Allrightsreserved.NoportionofthiscanbereproducedwithouttheexpresswrittenconsentofPremierFarnellCorporation.revised:10/10OPERATINGINSTRUCTIONS:Thetillerbarandtheupperandlowerbrakeknobsareusedtocontrolthemonitor.Tochangethehorizontalmonitorpo-sitiontowardthe“RIGHT”or“LEFT”,getafirmgriponthetillerbarhandleandturnthelowerbrakeknobcounterclock-wiseuntiltheunitcanbeeasilyrotated.Turnthesameknobclockwisetolocktheunitinthedesiredhorizontalposition.Tochangetheverticalmonitorpositionupwardordownward,getafirmgriponthetillerbarhandleandturntheupperbrakeknobcounterclockwiseuntiltheunitcanbeeasilyelevatedorlowered.Turnthesameknobclockwisetolocktheunitinthedesiredelevationposition.CAUTIONS:Yourmonitorandnozzleshouldbeinspectedpriortoandaftereachusetoensureitisingoodoperatingcondition.Periodically,anunanticipatedincidentoccurswheretheunitismisusedinamannerthatisinconsistentwithstandardoperatingpractices.Apartiallistofpotentialmisusesincludes:•Operatingabovemaximumratedpressureorflow.•Notdrainingandallowingwatertofreezeintheunit.•Prolongedexposuretotemperaturesabove140degreesF,orbelow-40degreesF.•Operatinginacorrosiveenvironment.•Othermisusethatmaybeuniquetoyourspecificenvironment.Also,therearemany“telltale”signsthatindicaterepairisinorder,suchas:•Abrakeknobthatisinoperableordifficulttooperate.•Excessivewear.•Poordischargeperformance.•Waterleaks.Ifanyoftheabovesituationsareencountered,themonitorshouldbetakenoutofservice,repairedandtestedbyaqualifiedtechnicianbeforeplacingitbackinservice.MAINTENANCEINSTRUCTIONS:•PeriodicallylubricatethegreasefittingswithLubriplateLow-Temporequivalent.Injectthelubricantuntilitbecomesvisiblefromthebleederholesinthecenteroftheswivelplugs.•Periodicallycleangritanddirtfromaroundexteriormovingparts.•Periodicallyoperateallfunctionsofthemonitorthroughitsfulltravel.•Thebrakemechanismonthehorizontalandverticaltravelmayrequireperiodicmaintenance.Tochecktheadjustment,rotatethebrakeknobcounterclockwiseuntilitstops.Turningthebrakeknobclockwise1to11/2turnsshouldlockthemonitor.Ifthemonitordoesnotlock,removethelockmechanism,inspectforwearandreplacecomponentsasnecessary.•Replacetheidentificationtagifitiswornordamaged.Figure1TrillerBarUpperBrakeKnob(Elevation)LowerBrakeKnob(Rotation)