回弹法检测混凝土抗压强度技术规程TechnicalSpecificationforInspectingofConcreteCompressiveStrengthbyReboundMethod(征求意见稿)2目次1总则·······························································································12术语、符号···················································································23回弹仪···························································································43.1技术要求·················································································43.2检定·························································································43.3保养·························································································54检测技术························································································64.1一般规定··················································································64.2回弹值测量···············································································74.3碳化深度值测量·······································································75回弹值计算·····················································································96混凝土强度推定············································································137检测报告·······················································································15附录A:江苏地区混凝土强度换算值表·············································16附录B:回弹法测试记录表································································22本规程用词说明·············································································23条文说明·····························································································2431总则1.0.1为适应江苏地区采用非破损方法检测结构混凝土抗压强度的要求,保证检测工作规范性和检测的精度要求,制定本规程。1.0.2本规程适用于龄期14~1800d,强度为10~60MPa结构混凝土抗压强度检测,但不适用于因冻害、化学侵蚀、火灾等造成表面疏松、剥落的结构混凝土强度检测。1.0.3混凝土强度验收和评定应按国家现行标准《混凝土结构工程施工及验收规范》(GB50204)、《混凝土强度检验评定标准》(GB/T50107)等相关标准执行,当对实体混凝土强度有疑义或有检测要求时,可采用本规程的方法进行检测,并作为混凝土结构处理的依据之一。1.0.4现场作业应遵守现行安全劳保和环境保护条例。1.0.5按本规程进行检测的人员,应经过专业技术培训。1.0.6结构混凝土抗压强度检测,除应符合本规程外,尚应符合国家现行有关的标准规定。42术语、符号2.1术语2.1.1回弹法根据结构或构件混凝土上测得的回弹值和碳化深度值来推定该结构或构件混凝土强度的方法。2.1.2测区检测构件混凝土强度时的一个检测单元。2.1.3测点测区内的一个回弹检测点。2.1.4测区混凝土强度换算值由测区的平均回弹值和碳化深度值通过测强曲线换算得到的测区现龄期混凝土强度值。2.1.5混凝土强度推定值相应于强度换算值总体分布中保证率不低于95%的构件中的混凝土强度值。2.2符号iR—第i个测点的回弹值。mR—测区或试块的平均回弹值。mR—回弹仪非水平状态检测时,测区的平均回弹值。tmR—回弹仪在水平方向检测混凝土浇筑表面时,测区的平均回弹值。bmR—回弹仪在水平方向检测混凝土浇筑底面时,测区的平均回弹值。taR—回弹仪检测混凝土浇筑表面时,回弹值的修正值。baR—回弹仪检测混凝土浇筑底面时,回弹值的修正值。5aR—非水平状态检测时,回弹值的修正值。id—第i次测量的碳化深度值。imd,—测区的平均碳化深度值。ci,cuf—测区混凝土强度换算值。ccufm—测区混凝土强度换算值的平均值。ccufmin,—构件中最小的测区混凝土强度换算值。1,ecuf—构件混凝土强度第一条件值(MPa);计算至0.1Mpa。2,ecuf—构件混凝土强度第二条件值(MPa);计算至0.1Mpa。ccufs—同批构件测区混凝土强度换算值的标准差。e,cuf—构件混凝土强度推定值。icorf,—对应第i个芯样的测区混凝土强度换算值。—修正系数。63回弹仪3.1技术要求3.1.1回弹仪可为数字式的,也可为指针直读式的。3.1.2回弹仪应具有产品质量合格证和省级法定检验单位的检定证书,并应在回弹仪的明显位置上标注名称、型号、制造厂名(或商标)、出厂编号等。3.1.3质量合格的回弹仪,应符合下列标准状态的要求:1水平弹击时,弹击锤脱钩的瞬间,回弹仪的标称动能应为2.207J;2弹击锤与弹击杆碰撞的瞬间,弹击拉簧应处于自由状态,此时弹击锤起跳点应相应于刻度尺上的“0”处;3在洛氏硬度HRC为60±2的钢砧上,回弹仪的率定值[R]应为80±2;4数字式回弹仪应带有指针直读示值系统;数字显示的回弹值与指针直读示值相差不应超过1。3.1.4回弹仪使用时的环境温度应为(-4~40)℃。3.2检定3.2.1回弹仪有下列情况之一时,应送法定检定单位检定,检定合格的回弹仪应具有检定合格证书,其有效期为半年。1新回弹仪启用前;2超过检定有效期限;73数字式回弹仪数字显示的回弹值与指针直读示值相差大于1;4主要零件更换后;5经常规保养后率定值不合格;6遭受严重撞击或其它损害。3.2.2回弹仪有下列情况之一时,应进行率定试验;1进行构件测试前后,如连续数天测试,可在每天测试完毕后率定一次;2测定过程中对回弹值有怀疑时。如率定回弹值不符合80±2范围内,应按第3.3.2条的要求对回弹仪进行常规保养后再率定,如仍不合格,应送检定单位检定。3.2.3回弹仪的率定试验应符合下列规定:1率定试验应在室温为(5~35)℃的条件下进行;2钢砧表面应干燥、清洁,应稳固地平放在刚度大的物体上;3回弹值应取连续向下弹击三次的稳定回弹结果的平均值;4率定试验应分四个方向进行,且每个方向弹击前,弹击杆应旋转90度,每个方向的回弹平均值均应为80±2。3.2.4率定回弹仪的钢砧应每2年送授权计量检定机构检定或校准。83.3保养3.3.1回弹仪有下列情况之一时,应进行常规保养;1弹击超过2000次;2对测试值有怀疑时;3率定值不符合要求。3.3.2常规保养应符合下列要求;1使弹击锤脱钩后,取出机芯,然后卸下弹击杆、缓冲压簧、弹击锤(连同弹击拉簧和拉簧座)、刻度尺、指针轴和指针;2用清洗剂清洗机芯的中心导杆、弹击拉簧、拉簧座、弹击杆及其内孔,缓冲压簧、弹击锤及其内孔和冲击面、指针块及其内孔、指针片、指针轴、刻度尺、卡环以及机壳的内壁和指针导槽等;经过清洗后的零部件,除中心导杆薄薄地抹上一层清洁机油外,其他部件均不得抹油;3清理机壳内壁,检查指针,其摩擦力应为(0.5~0.8)N;4对于数字式回弹仪,还应按产品要求的维护程序进行维护;5保养时应保持弹击拉簧前端钩入拉簧座的原孔位,不得旋转尾盖上已定位紧固的调零螺丝,不得自制或更换零部件;96保养后,应按3.2.3条的要求进行率定试验。3.3.3回弹仪每次使用完毕后应及时保养。使弹击杆伸出机壳,清除弹击杆(包括其前球端面)以及刻度尺表面和外壳上的污垢、尘土。3.3.4回弹仪不用时,应将弹击杆压入机壳内,弹击后应使弹击锤脱钩,按下按钮,锁住机芯,将回弹仪装入套筒,储存在干燥阴凉处。104检测技术4.1一般规定4.1.1检测混凝土强度的结构或构件宜具有下列资料:1工程名称及设计、施工、建设、监理单位名称、混凝土生产厂家;2结构或构件名称、数量及混凝土强度等级;3水泥安定性,外加剂、掺合料品种,混凝土配合比等;4模板类型、成型日期、混凝土浇筑及养护情况等;5必要的设计图纸、施工记录和相关验收资料;6结构或构件质量及存在问题;7环境条件,包括:结构或构件位置,遭受浸水、冻害、高温、腐蚀及其他自然灾害等情况。4.1.2混凝土强度可按单个构件或按批量进行检测,应遵守下列规定:1用于推定单个构件:应符合本规程4.1.3条的规定;2用于推定批量构件:对于混凝土生产工艺、强度等级相同,原材料、配合比、养护条件基本一致且龄期相近的一批同类构件,应随机抽取构件,抽检数量不宜少于同批构件总数的30%,且不宜少于10个构件。当检验批构件数量大于30个时,抽样构件数量可适当调整,并不得少于国家现行有关标准规定的最少抽样数量。4.1.3单个构件的检测应符合下列要求:111对于一般构件,测区数不宜少于10个;当受检构件某一方向尺寸不大于4.5m且另一方向尺寸不大于0.3m时,构件的测区数量可适当减少,但不应少于5个;2相邻两测区的间距不应大于2m,测区离构件端部或施工缝边缘的距离不宜大于0.3m,且不宜小于0.2m;3测区宜选在混凝土浇筑的侧面,如不能满足这一要求时,可选在使回弹仪处于非水平方向的混凝土浇筑的顶面或底面;4测区宜选在构件的两个对称可测面上,当不能满足这一要求时,也可选在一个可测面上,且应均匀分布;5一个测区的面积,以能容纳16个回弹测点为宜,一般约为0.04m2的正方形;6测区表面应清洁、平整、干燥,不应有接缝、饰面、粉刷层、浮浆、油垢、蜂窝、麻面等,必要时可用砂轮清除表面的疏松层杂物和不平整处,磨光的测面不应有残留的粉末或碎屑;7对弹击时产生颤动的薄壁、小型构件应进行固定。4.1.4构件及测区均应标有清晰的编号,必要时应在记录纸上描述测区在构件上的位置和外观质量情况。4.1.5测试条件不能完全满足下列要求:1混凝土采用的水泥、砂石、外加剂、掺合料、拌合用水符合国家现行有关标准;122采用普通成型工艺;3采用符合国家标准规定的模板;4蒸汽养护出池经自然养护7d以上,且混凝土表层为干燥状态;5自然养护且龄期为(14~1800)d;6抗压强度为(10~60)MPa。允许采用从结构或构件上钻取混凝土芯样或同条件试块对测区混凝土强度换算值进行修正。对同一强度等级混凝土修正时,钻取芯样数量不应少于6个,公称直径宜为100