一、楼面恒荷载统计壹.地砖楼面1.地暖地砖楼面(客厅、餐厅、卧室、厨房):做法厚度:100mm10厚地板砖0.01*25=0.25KN/M220厚1:4水泥砂浆保护层0.02*20=0.40KN/M250厚C15细石砼垫层0.05*24=1.20KN/M220厚聚苯板保温层0.02*0.5=0.01KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+1.20+0.01+0.2=2.06KN/M2取2.1KN/M22.地砖楼面(适用于防滑地砖):做法厚度:50mm10厚地砖0.01*25=0.25KN/M225厚1:3干硬性水泥砂浆粘结层0.025*20=0.50KN/M215厚1:3水泥砂浆找平层0.015*20=0.30KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.5+0.3+0.2=1.25KN/M23.地砖楼面(适用于防滑地砖):做法厚度:50mm5厚地砖0.005*25=0.125KN/M230厚1:3干硬性水泥砂浆粘结层0.030*20=0.60KN/M215厚1:3水泥砂浆找平层0.015*20=0.30KN/M2板底抹灰0.2KN/M2ΣGk=0.125+0.6+0.3+0.2=1.225KN/M2取1.25KN/M24.地砖楼面:做法厚度:30mm10厚地砖0.01*25=0.25KN/M220厚1:2水泥砂浆粘结层0.02*20=0.40KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.2=0.85KN/M25.地砖楼面:做法厚度:100mm10厚地砖0.01*25=0.25KN/M220厚1:4干硬性水泥砂浆粘结层0.02*20=0.40KN/M270厚CL7.5轻集料混凝土垫层(焦渣混凝土)0.07*12=0.84KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.84+0.2=1.69KN/M2取1.7KN/M26.地砖楼面:做法厚度:100mm10厚地砖0.01*25=0.25KN/M230厚1:3干硬性水泥砂浆粘结层0.03*20=0.60KN/M260厚CL7.5轻集料混凝土垫层(焦渣混凝土)0.06*12=0.72KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.6+0.72+0.2=1.77KN/M2取1.8KN/M27.防滑地砖楼面(一般阳台处):做法厚度:80mm10厚地砖0.01*25=0.25KN/M220厚1:4干硬性水泥砂浆粘结层0.02*20=0.40KN/M21.5厚聚合物水泥基防水涂料0.0015*20=0.003KN/M245厚C15细石砼找坡,最薄处350.045*24=1.08KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.003+1.08+0.2=1.933KN/M2取1.95KN/M28开敞阳台:做法厚度:80mm10厚地板砖0.01*25=0.25KN/M250厚C15细石砼找坡,最薄处300.05*24=1.2KN/M220厚挤塑聚苯板0.02*0.5=0.01KN/M2板底抹灰0.2KN/M2ΣGk=0.25+1.2+0.01+0.2=1.66KN/M2取1.7KN/M29.花岗岩楼面:做法厚度:50mm20厚花岗石板0.02*28=0.56KN/M230厚1:3干硬性水泥砂浆粘结层0.03*20=0.60KN/M2板底抹灰0.2KN/M2ΣGk=0.56+0.6+0.2=1.36KN/M2取1.4KN/M210.普通卫生间楼面:做法厚度:80mm10厚地板砖0.01*25=0.25KN/M220厚水泥砂浆结合层0.02*20=0.40KN/M235厚C20细石砼找坡、最薄处200.035*24=0.84KN/M21.5厚聚氨酯涂膜防水层0.0015*20=0.03KN/M215厚水泥砂浆结合层0.015*20=0.30KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.84+0.03+0.3+0.2=2.02KN/M2取2.1KN/M211地暖卫生间楼面:做法厚度:140mm10厚地板砖0.01*25=0.25KN/M220厚水泥砂浆结合层0.02*20=0.40KN/M22厚聚氨酯防水层0.002*20=0.04KN/M250厚C15细石砼找坡、最薄处200.05*24=1.20KN/M220厚聚苯板保温层0.02*0.5=0.01KN/M215厚水泥砂浆结合层0.015*20=0.30KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.04+1.2+0.01+0.30+0.2=2.40KN/M2取2.4KN/M2贰.水泥楼面1.水泥楼面:做法厚度:30mm30厚1:2.5水泥砂浆压实赶光0.03*20=0.60KN/M2板底抹灰0.2KN/M2ΣGk=0.60+0.2=0.80KN/M22水泥楼面:做法厚度:50mm20厚1:2.5水泥砂浆压实赶光0.02*20=0.40KN/M230厚1:3干硬性水泥砂浆粘结层0.03*20=0.60KN/M2板底抹灰0.2KN/M2ΣGk=0.40+0.60+0.2=1.20KN/M23.机房层楼面1:做法厚度:50mm50厚C20细石混凝土0.05*24=1.2KN/M2板底抹灰0.2KN/M2ΣGk=1.2+0.2=1.40KN/M24.机房层楼面2:做法厚度:100mm100厚C20细石混凝土0.10*24=2.4KN/M2板底抹灰0.2KN/M2ΣGk=2.4+0.2=2.6KN/M2注意:以上各项板底抹灰是根据住宅常用做法取值。对于板底抹灰厚度大于10mm或者吊顶要根据实际工程情况确定,其他数值不变。弎.屋面、1不上人屋面1:20厚水泥砂浆保护层0.02*20=0.40KN/M2防水层(3+3高聚物改性沥青防水卷材)0.50KN/M220厚水泥砂浆结合层0.02*20=0.40KN/M2水泥珍珠岩找2%坡,最薄处30厚(0.15+0.03)/2*6=0.54KN/M270厚聚苯保温层0.07*0.5=0.035KN/M2板底抹灰0.2KN/M2ΣGk=0.4+0.5+0.4+0.54+0.035+0.2=2.075KN/M2取2.1KN/M2、2.不上人屋面2:50厚C20细石混凝土0.05*24=1.2KN/M20.4厚聚氯乙烯塑料薄膜隔离层0.0004*20=0.008KN/M260厚聚苯保温层0.06*0.5=0.03KN/M2柔性防水层0.50KN/M220厚DS砂浆找平层0.02*20=0.40KN/M2复合轻集料垫层2%坡,最薄处30厚(0.15+0.03)/2*12=1.08KN/M2板底抹灰0.2KN/M2ΣGk=1.2+0.008+0.03+0.5+0.4+1.08+0.2=3.418KN/M2取3.5KN/M23.上人屋面1:10厚地板砖0.01*25=0.25KN/M220厚1:4干硬性水泥砂浆0.02*20=0.40KN/M2防水层(3+3高聚物改性沥青防水卷材)0.50KN/M220厚1:3水泥砂浆找平层0.02*20=0.40KN/M2水泥珍珠岩找2%坡,最薄处30厚(0.15+0.03)/2*6=0.54KN/M280厚聚苯保温层0.08*0.5=0.04KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.5+0.4+0.54+0.04+0.2=2.33KN/M2取2.5KN/M24.露台:10厚地板砖0.01*25=0.25KN/M220厚1:4干硬性水泥砂浆0.02*20=0.40KN/M230厚C20细石混凝土0.03*24=0.72KN/M2防水层(3+3高聚物改性沥青防水卷材)0.50KN/M2水泥珍珠岩找2%坡,最薄处30厚(0.15+0.03)/2*6=0.54KN/M270厚聚苯保温层0.07*0.5=0.035KN/M2板底抹灰0.2KN/M2ΣGk=0.25+0.4+0.72+0.5+0.54+0.035+0.2=2.645KN/M2取2.7KN/M2注意:1、以上各项板底抹灰是根据住宅常用做法取值。对于板底抹灰厚度大于10mm或者吊顶要根据实际工程情况确定,其他数值不变。2、屋面单坡长度按7.5米考虑,如单坡长度大于7.5米,应按实际情况计算找坡层荷载。肆.空调吊顶等附加荷载如有中央空调吊顶的一般需要在以上恒载上另加0.5KN/M2二、线恒荷载统计页岩砖:22(容重)X墙宽X墙高+20X0.04X墙高陶粒空心砌块:8(容重)X墙宽X墙高+20X0.04X墙高蒸压粉煤灰加气混凝土砌块:6(容重)X墙宽X墙高+20X0.04X墙高三、特殊需要注意的活载其他详荷载规范GB50009-2012第5.1.1条及技术措施)多层住宅楼梯:2.0KN/M2其他所有楼梯:3.5KN/M2上人屋面:2.0KN/M2不上人屋面:0.5KN/M2带浴缸卫生间:4.0KN/M2带隔墙蹲厕:8.0KN/M2地下室顶板施工活载:5.0KN/M2制冷机房活载:8.0KN/M2水泵房、变配电房活载:10.0KN/M2发电机房活载:10.0KN/M2四、设计中需要注意的细节注:1、工业建筑楼面活荷载应根据实际使用情况取值,且活荷载不应按《荷载规范》GB50009-2012第5.1.2条进行折减。2、民用建筑墙、柱和基础设计时楼面活荷载折减系数取值应注意《荷载规范》GB50009-2012表5.1.2适用范围,根据不同的建筑类别对软件折减系数进行修改。3、工业建筑设计应注意是否有屋面积灰荷载,积灰荷载应与雪荷载或不上人的屋面均布活荷载两者中的较大值同时考虑。4、屋面天沟和设有卷沿的雨蓬应考虑充满水时的荷载,当天沟深度超过500时,宜在天沟侧板适当位置增设水孔,此时水重可计至溢水孔。此外水沟设计时尚应考虑找坡层的重量。5、高底层相邻的屋面,在设计低层屋面构件时应适当考虑施工临时荷载,该荷载应不小于4KN/m2,并在施工图上注明。6、室内地下室顶板须考虑施工时堆放材料或作临时工场的荷载,该荷载宜控制在5KN/m2。7、计算地下室外墙时候,其室外地面荷载取值不宜低于10KN/m2,如室外地面为行车道则应考虑行车荷载。8、坡屋面恒荷载计算:按实际做法算出恒载后除以cosa得出水平投影恒载,活载直接采用规范数值即可。9、高低跨屋面及有女儿墙或其他突起物的屋面应根据荷载规范GB50009-2012第7.2.1条考虑积雪荷载。10、轻钢结构当采用压型钢板轻型屋面时,屋面竖向均布活荷载的标准值应取0.5KN/M2,对受荷水平投影面积大于60平米的刚架构件,屋面竖向均布活荷载的标准值可取不小于0.3KN/M2;刚架计算时活荷载取屋面活载和100年重现期雪压两者较大值。屋面檩条计算时,活荷载应取0.5KN/M2。