10kV高压开关柜安装作业指导书

整理文档很辛苦,赏杯茶钱您下走!

免费阅读已结束,点击下载阅读编辑剩下 ...

阅读已结束,您可以下载文档离线阅读编辑

资源描述

七里塘水电站10kV高压开关柜安装作业指导书2013年9月15日黔东水力发电总厂10kV高压开关柜安装作业指导书-1-高压开关柜安装作业指导书目次1高压开关柜安装工程简述·································································22编写依据···············································································23作业流程···············································································24作业方法···············································································35质量控制措施···········································································56单元工程质量评定表·····································································5附表一:固定式手车式高压开关柜安装单元工程质量评定表附表二:互感器安装单元工程质量评定表附表三:避雷器安装单元工程质量评定表附表四:硬母线安装单元工程质量评定表1高压开关柜安装工程简述1.1高压开关柜安装概述本工程安装项目包括基础检查、设备开箱检查、盘柜就位安装、母线安装、断路器及隔离开关调整、交接试验。黔东水力发电总厂10kV高压开关柜安装作业指导书-2-1.2高压开关柜安装特点七里塘水电站桥机共安装12面型号为KYN28A-12的金属铠装移开式开关柜(含2台高压限流熔断器柜),额定电压:12kV,额定绝缘水平:1min工频耐压42kV、雷冲击耐压75kV,电流参数:主母线额定电流为主变低压侧进线柜≥2500A(其余≥1200A)、额定短时耐受电流≥50kA/3s、额定峰值耐受电流≥125kA,防护等级:≥IP4X,耐受地震能力:Ⅷ度。安装工作在基础交面后进行。整个安装工程可分为盘柜就位安装、母线安装、断路器及隔离开关调整、交接试验。2编写依据表2-1编写依据序号引用资料名称1厂家图纸及技术文件2七里塘高低压设备招标文件3GBJ147—1990《电气装置安装工程高压电器施工及验收规范》4DL408—1991《电业安全工作规程(发电厂和变电所电气部分)》5DL5009.3—1997《电力建设安全工作规程》6Q/CSG10007—2004《电力设备预防性试验规程》7《10kV~500kV输变电及配电工程质量验收与评定标准》8Q/CSG11105.2—2008《南方电网工程施工工艺控制规范》3作业流程作业(工序)流程见图3-1。黔东水力发电总厂10kV高压开关柜安装作业指导书-3-图3-1作业(工序)流程图4作业方法4.1施工准备4.1.1技术准备:按规程、生产厂家安装说明书、图纸、设计要求及施工措施对施工人员进行技术交底,交底要有针对性。4.1.2人员组织:技术负责人、安装负责人、安全质量负责人和技术工人。4.1.3机具的准备:按施工要求准备机具,并对其性能及状态进行检查和维护。4.1.4施工材料准备:焊条、螺栓、油漆等。4.2基础检查4.2.1用经纬仪及钢卷尺对开关柜基础进行核对尺寸,检查基础槽钢长度、宽度、标高及相对位置是否符合设计要求,以及检查基础槽钢的直线度和水平度,误差不得超过允许值;检查高压及控制电缆的孔洞是否对应开关柜的排列布置。4.2.2清除基础槽钢面上的灰砂,完成槽钢的接地工作,测量基础槽钢的水平度和不直度,找出最高点,并标注高差,开关柜宜从中间开始就位。4.3搬运及开箱检查4.3.1现场搬运盘柜。(1)开关柜的搬运设专人指挥,配备足够的施工人员,以保证人身和设备安全。(2)根据现场情况,设备的搬运、移动采用推车进行。搬运时,用吊车将开关柜吊到推车上,然后一人拉推车的把手,3人合力推柜体,1人专门负责观察推车行走的路线,防止推车的轮子掉到孔洞里及防止柜体倾覆。(3)盘柜搬运时应按图纸将盘柜按顺序摆放,以方便下一步盘柜的就位安装。4.3.2设备检查时生产厂家、监理及业主代表应在现场。检查的主要内容:检查表面有无刮伤或撞击痕迹,对照设计图纸及核对到货清单、检查设备型号、规格、数量是否相符,以及随柜而到的有关附件、备件、仪表、仪器、专用工具的数量及规格与清单是否相符;特别对于瓷绝缘子等瓷件更应该认真检查有无变形、破损、受潮;检查厂家出厂技术文件是否齐全;如在检查中发现的缺损件、厂家资料不齐全等应在开箱检查记录上填好,由在现场生产厂家、监理及业主代表签名见证,通知厂家补回。4.4盘柜就位安装4.4.1首先根据设计的尺寸拉好整排屏柜的直线。按设计位置和尺寸把第一块盘用线锤和水平尺进行找正,按规范盘柜垂直度误差应小于每米1.5mm,如达不到要求可在柜底垫垫块,但垫块不能超过三块且垫块不能有松动,达到要求后,在开关柜的四个底角上烧焊或钻孔用螺栓将其固定。4.4.2第一面开关柜安装好后,其他开关柜就按第一个柜作为标准拼装起来。通常10kV配电盘柜以主变压器进线盘柜为第一面柜开始安装,然后分别向两侧拼装。如发现基础槽钢的水平误差较大,应选主变压器进线柜第一面柜的安装位置。4.4.3依次将盘逐块找正靠紧。检查盘间螺丝孔应相互对应,如位置不对可用圆锉修整。黔东水力发电总厂10kV高压开关柜安装作业指导书-4-带上盘间螺丝(不要拧紧),以第一块盘为准,用撬棍对盘进行统一调整,调整垫铁的厚度及盘间螺丝松紧,使每块盘达到规定要求,依次将各盘固定。最后要求成列柜顶水平高差不大于5mm,成列柜面不平度小于5mm,柜间缝隙小于2mm。4.5开关柜内母线安装4.5.1柜内母线厂家已配备。柜体间联络母线安装应按分段图、相序、编号、方向和标志正确放置;母线的搭接面应连接紧密,并应在接触面上涂一层电力复合脂。连接螺栓用力矩扳手紧固,其紧固力矩值应符合如表4-1所示的规定。表4-1钢制螺栓的紧固力矩值螺栓规格(mm)力矩值(N·m)螺栓规格(mm)力矩值(N·m)M88.8~10.8M1678.5~98.1M1017.7~22.6M1898.0~127.4M1231.4~39.2M20156.9~196.2M1451.0~60.8M24274.6~343.24.5.2封闭母线桥由生产厂家到现场实测尺寸并在厂制作好后再送往现场安装,安装前先搭设好脚手架,根据母线桥安装高度搭设至合适高度,根据安装图纸将母线箱逐个抬上脚手架摆放,拼装连接时从两端往中间靠拢连接,用短木方调整母线箱安装高度,在设有吊杆处用吊杆调整母线箱高度及水平度,拼接过程中不宜将两个母线箱之间的螺栓紧固,应留有一定的间隙,以便统一调整母线桥的间隙分布,整个母线箱拼接完成后检查整体水平度和拼装间隙的分布,调整后逐步将螺栓紧固,并让吊杆处于适当的受力状态。4.5.3母线安装应符合下列要求:(1)交流母线的固定金具或其他支持金具不应成闭合磁路。(2)当母线平置时,母线支持夹板的上部应与母线保持1~1.5mm的间隙;当母线立置时,上部压板应与母线保持1.5~2mm的间隙。(3)母线对地及相与相之间最小电气距离应符合规程中的规定:10kV不小于125mm。(4)母线桥安装时应注意母线桥体的美观,保证横平竖直,桥体与桥体、柜体驳接处的缝隙应小于2mm。(5)母线安装完成后进行核相。4.6断路器及隔离开关的调整4.6.1断路器的调整:高压开关柜内真空断路器生产厂家已调整好,在现场不准自行解体调整,如检查到有些断路器的机械特性参数不符合要求,应立即通知生产厂家到现场调整。4.6.2隔离开关的调整:检查隔离开关是否满足规范要求,如达不到要求,应通知生产厂家到现场调整。隔离开关的具体检查项目:三相同期性,触头是否偏心,触头与触指的接触情况。注:小车式无上、下隔离开关,只有接地开关,调整方法与上述类同。4.7安装后注意事项高压柜安装完后,要全面地进行检查,清理工作现场的工具。5质量控制措施5.1质量控制措施5.1.1基础预埋槽钢的直线度误差应不超过每米1mm,全长不超过5mm;水平度误差不超过每米1mm,全长不超过5mm。预埋槽钢应在土建施工阶段进行预埋质量控制,在预埋槽钢二次灌浆前应确认预埋质量符合要求后进行二次灌浆。5.1.2高压柜体拼装的垂直度误差不大于1.5mm;成排水平度误差不超过5mm;成排表面黔东水力发电总厂10kV高压开关柜安装作业指导书-5-不平度不超过5mm;柜体间缝隙应不大于2mm。用垫铁调整水平度时,同一位置的垫铁的数量不能超过三块且不能有松动。5.1.3母线安装应符合下列要求:(1)交流母线的固定金具或其他支持金具不应成闭合磁路。(2)当母线平置时,母线支持夹板的上部应与母线保持1~1.5mm的间隙;当母线立置时,上部压板应与母线保持1.5~2mm的间隙。(3)母线对地及相与相之间最小电气距离应符合规程中的规定:10kV不小于125mm。(4)母线桥安装时应注意母线桥体的美观,保证横平竖直,桥体与桥体、柜体驳接处的缝隙应小于2mm。(5)柜内一次接地母线必须明显可靠接地。5.1.4母线固定螺栓的紧固应到达如表4-1所示规定的力矩值。在母线验收合格后应对所有螺栓进行紧固检查,确认达标的用油性笔画上记号,防止个别螺栓没有紧固。5.1.5真空断路器的安装(其主要技术指标见表5-1)表5-1真空断路器的主要技术指标主要指标标准值主要指标标准值触头开距(mm)国产泡11±1进口泡8±1接触行程(mm)4±1油缓冲行程(mm)7~10三相不同期性(ms)小于2注:断路器在出厂时生产厂家已经调整好,现场只需进行检查,如有问题须联系生产厂家到场处理。5.1.6隔离开关的具体检查项目:三相同期性误差不得大于5mm,触头不偏心,触头与触指的接触情况、插入深度等应符合制造厂规定。5.1.7高压开关柜安装后表面应保护油漆完好,表面无剥落生锈、划痕、碰损等。柜内应干净,无积尘。5.1.8断路器操动机构各部件工作正常,隔离开关操作灵活、无卡阻现象。“五防”闭锁功能良好无损坏。6单元工程质量评定表附表一:固定式手车式高压开关柜安装单元工程质量评定表附表二:互感器安装单元工程质量评定表附表三:避雷器安装单元工程质量评定表附表四:硬母线安装单元工程质量评定表黔东水力发电总厂10kV高压开关柜安装作业指导书-6-固定式手车式高压开关柜安装单元工程质量评定表附表一单位工程名称10kV高压开关柜安装工程单元工程量分部工程名称101KV高压开关柜安装工程施工单位贵州黔水建设工程有限公司单元工程名称、部位高压开关柜安装检验日期年月日质量检查记录序号检查项目检查标准结论1基础型钢埋设1.1允许偏差直度:1/m,5/全长水平度:1/m,5/全长1.2型钢接地接地可靠,安装后其顶部宜高出抹面102开关柜本体安装2.1允许偏差垂直度:1.5/m平度:相邻两柜边1,成列柜面5柜间间隙:22.2柜体固定牢固,柜间连接紧密2.3与建筑物间距离应符合设计要求2.4隔板完整牢固,门锁灵活,齐全3△柜内电气设备安装主要电气设备应分别填写单元工程质量评定表评定质量4接地固定牢固,接触良好,排列整齐,柜门等应采用软铜线接地5手车式开关柜5.1本体安装工作和试验位置的定位应准确可靠△5.2手车推拉灵活,接地触头接触良好5.3机械闭锁装置动作正确可靠5.4动静触头中心线一致,触头接触紧密5.5触头间隙推入工作位置后,应符合产品的技术要求5.6辅助开关切换接点接点动作准确,接触可靠5.7安全隔板开放灵活,正确5.8柜内照明齐全6二次回路所有二次回路接线应符合设计要求,连接可靠,标志齐全清晰,绝缘电阻大于等于0.5MΩ检验结果共检验项,合格项,其中优良项,优良率%评定意见单元工程质量等级主要检查项目全部符合质量标准,一般检查项目中

1 / 11
下载文档,编辑使用

©2015-2020 m.777doc.com 三七文档.

备案号:鲁ICP备2024069028号-1 客服联系 QQ:2149211541

×
保存成功